Indoor unit outdoor unit – Toshiba RAV-SM800XT-E User Manual

Page 10

Advertising
background image

– 8 –

3-2. RAV-SM800XT-E / RAV-SM800AT-E

Indoor unit

Outdoor unit

TCJ

sensor

Air heat exchanger

Strainer

Strainer

TC sensor

Refrigerant pipe
at liquid side
Outer dia.

B

Refrigerant pipe
at gas side
Outer dia.

A

Packed valve

Outer dia.

B

Packed valve

Outer dia.

A

Max

50m

TS sensor

Accumulator

(1500cc)

TD sensor

TO sensor

TE

sensor

4-way valve

(STF-0213Z)

25 x L160

Rotary compressor

(DA220A2F-20L)

Heat exchanger

8

1 row 30 stages
FP1.3 flat fin

Modulating (PMV)
(SKV-18D26)

Capillary

3 x

2

x L530

25 x L210

Muffler

R410A 1.5 kg

Cooling
Heating

Ps

Pd

Pressure

Pipe surface temperature (

°

C)

(MPa)

Discharge

Suction

Indoor heat Outdoor heat

Indoor

exchanger

exchanger

fan

Pd

Ps

(TD)

(TS)

(TC)

(TE)

Indoor

Outdoor

Standard

3.3

0.9

89

8

8

40

64

HIGH

27/19

35/–

Cooling

Overload

3.7

1.1

87

17

14

46

45

HIGH

32/24

43/–

Low load

1.0

0.8

22

2

1

1

24

LOW

18/15.5

–5/–

Standard

3.3

0.6

93

0

54

0

70

HIGH

20/–

7/6

Heating

Overload

3.1

1.1

75

20

52

15

24

LOW

30.–

24/18

Low load

2.0

0.2

90

–26

25

–25

90

HIGH

0

–20/(70%)

Indoor/Outdoor

temp. conditions

(DB/WB) (

°

C)

Compressor

revolutions
per second

(rps)

*

* 4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

Outer diameter of refrigerant pipe

Gas side

A

Liquid side

B

9.5 mm

15.9 mm

Advertising