background image

– 53 –

NO

Correct connection of connector.

* For RAV-SM560AT-E, replace the control B.C. board

* Refer to Characteristics-3.

YES

NO

Are characteristics of TE/TS sensor

resistance values normal?

Replace TE and TS sensors.

YES

* (For RAV-SM560AT-E, CN600TE sensor and CN603 TS sensor)

Are connections of

TE/TS sensor connectors of

CDB CN604/CN605 normal?

Check CDB.
Defect Replace

* Refer to Characteristics-4.

NO

Correct connection of connector.

YES

NO

Are characteristics of TD sensor

resistance value normal?

Replace TD sensors.

YES

* (For RAV-SM560AT-E, CN601 on

control P.C. board)

Is connection of TD sensor connector

of CDB CN600 normal?

Check control P.C. board.
Defect Replace

Is there no abnormal overload?

Are cabling/connector normal?

Was the error just after

power ON determined?

Is IPDU P.C. board come to

closely contact with heat sink?

Improve and eliminate the cause.

Correct connection of connector.

Correct mounting.

Check cabling between IPDU
and CDB and connector.

IPDU P.C. board error
Defect Replace

IPDU P.C. board error
Defect Replace

NO

NO

NO

NO

YES

YES

YES

NO

YES

YES

Are connections of

CDB CN800 and CDB IPDU CN06

connectors normal?

[18 error]

[19 error]

[1C error]* Except RAV-SM560AT-E

Advertising