No.

†

Part name

Compressor

Procedure

1) Perform works of items



,

‚

,

ƒ

,

„

, and

…

.

2) Evacuate refrigerant gas.
3) Disconnect the connector for fan motor from

the inverter.

4) Take off screws fixing the motor base to the

bottom plate. (ST1T Ø4 x 10L, 2 pcs.)

5) Remove the motor base together with the

fan motor and the propeller fan.

6) Take off screws fixing the partition plate to

the valve support plate.
(ST1T Ø4 x 10L, 2 pcs.)

7) Remove the valve support plate.

(M6 x 4 pcs.)

8) Take off screws of the partition plate and the

bottom plate. (ST1T Ø4 x 10L, 2 pcs.)

9) Take off screws of the partition plate and the

heat exchanger. (ST1T Ø4 x 10L, 2 pcs.)

10) Remove the noise-insulator.

11) Remove the terminal covers of the com-

pressor, and disconnect lead wires of the
compressor and the compressor thermo
assembly from the terminal.

12) Remove pipes connected to the compres-

sor with a burner.

CAUTION

Pay attention to that flame does not involve
4-way valve or PMV. (If doing so, a malfunc-
tion may be caused.)

13) Pull the refrigerating cycle upward.
14) Take off nut fixing the compressor on the

bottom plate. (3 pcs.)

15) Pull the compressor toward you.

CAUTION

When reconnecting the lead wires to the
compressor terminals after replacement of
the compressor, be sure to caulk the Faston
terminal without loosening.

Remarks

Motor

base

Partition plate

Valve support

Screw

Partition

plate

Valve
support

Compressor
lead wire

Case thermo

Compressor
nut (3 pcs.)

Remove
(Suction
pipe)

Remove
(Discharge
pipe)