Table 10-2-2, No display in the setting at shipment – Toshiba RAV-SM800XT-E User Manual

Page 51

Advertising
background image

– 49 –

The serial signal is not output
from outdoor unit to indoor unit.

Miscabling of inter-unit cables

Defective serial sending circuit
on outdoor P.C. board

Defective serial receiving circuit
on outdoor P.C. board

Compressor case thermo
operation

BUS communication circuit error
* BUS communication was

interrupted over the specified
time.

Error in 4-way valve system

Indoor heat exchanger
temperature rise after start of
cooling operation.

Indoor heat exchanger
temperature fall after start of
heating operation.

Error in other cycles

Indoor heat exchanger temp
(TC) does not vary after start of
cooling/ heating operation.

Coming-off, disconnection or
short of indoor temp sensor (TA)

Coming-off, disconnection or
short of indoor temp sensor (TC)

Coming-off, disconnection or
short of indoor temp sensor
(TCJ)

Error in indoor fan system
Revolutions frequency error of fan

Error in indoor unit or other
positions
1. EEPROM access error

Outside error input
Detected by input voltage level
from outside devices

Outside interlock input
Detected by input voltage level
from outside devices

Table 10-2-2

Operation of diagnostic function

Judgement and action

Block

Check

Symptom

Unit

Condition

code

status

Operation
continues.

Operation
continues
(According
to remote
control of
indoor
unit)

Operation
continues.

Operation
continues.

Operation
continues.

Operation
continues.

Operation
continues.

All stop

Operation
continues.

Operation
continues.

All stop

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

1. Outdoor unit does not completely

operate.

Inter-unit cable check, correction of
miscabling

Outdoor P.C. board check, P.C. board
cables check

Compressor case thermo check

2. In normal operation

When outdoor sending serial LED
(Green) flashes, the receiving serial
LED (Orange) also flashes. : Indoor
P.C. board (Main P.C. board) check
When the receiving serial LED (Orange)
does not flash: Outdoor P.C. board
check

1. Communication line check, miscabling

check
Power supply check for central control
(Central control remote control, etc.)
and indoor unit

2. Communication check (XY terminal)
3. Indoor P.C. board check
4. Central control check

(Communication P.C. board)

1. Check 4-way valve.
2. Check 2-way valve and non-return

valve.

3. Check indoor heat exchanger sensor

(TC).

4. Check indoor P.C. board

(Main P.C. board).

1. Compressor case thermo operation.
2. Coming-off of detection part of indoor

heat exchanger sensor.

3. Check indoor heat exchanger sensor

(TC).

4. Check indoor P.C. board

(Main P.C. board).

1. Check indoor temp sensor (TA).
2. Check indoor P.C. board

(Main P.C. board).

1. Check indoor temp sensor (TC).
2. Check indoor P.C. board

(Main P.C. board).

1. Check indoor temp sensor (TCJ).
2. Check indoor P.C. board (Main P.C.

board).

1. Check indoor fan motor connector

circuit (CN210).

2. Check indoor fan.
3. Check indoor P.C. board

(Main P.C. board).

1. Check indoor P.C. board

(EEPROM and peripheral circuits)
(Main P.C. board).

1. Check outside devices.
2. Check indoor P.C. board

(Main P.C. board).

[MODE]
[TIMER] lamp
5Hz flash

[MODE] lamp
5Hz flash

[MODE] lamp
5Hz flash

*

*: No display in the setting at shipment