– 55 –

[21 error]

NO

NO

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

YES

NO

YES

Check charged refrigerant amount.

Check liquid/gas valves.

Check abnormal overload.

Is high-voltage

protective operation by

TE sensor normal?

* For RAV-SM560AT-E, check control P.C. board.

* Refer to Characteristics-3 and 4.

Is connection of

connector normal?

Is connection of cabling

connector normal?

Do not TD and TO sensors

come off the detection part?

Correct connection of
cabling connector.

Correct connection of
connector.

Check TE, TC, TS sensors.

Replace electron expansion valve.

Replace TD, TO,
and TC sensors.

Does cooling outdoor fan

normally operate?

Does electron control

valve normally operate?

Is fan motor normal?

Replace fan motor.

Correct coming-off.

Are characteristics of

TD, TO, TC sensor resistance

values normal?

Check CDB.
Defect Replace

Check TE sensor.
Defect Replace