Inverter over-current protective circuit
operates.
(For a short time)

Error on current detection circuit

Current value is high at AC side even
while compressor stops.

Phase of power supply is missed.

Coming-off, disconnection or short of
outdoor temp sensor

Coming-off, disconnection or short of
outdoor temp sensor

Compressor drive output error

Tin thermistor temp, Tin error
(IPDU heat sink temp. is high.)
Communication error between IPDU

Connector coming-off between CDB and
IPDU

Compressor does not rotate. (Over-current
protective circuit works when constant time
passed after activation of compressor.)

Discharge temp error

Discharge temp over specified value was
detected.

Compressor breakdown

Operation frequency lowered and stops
though operation had started.

High-voltage protection error by TE sensor

TE temp over specified value was
detected.

DC outdoor fan motor error

IDC operation or lock was detected by
DC outdoor fan driving.

Error on IPDU position detection circuit

Coming-off, disconnection or short of
outdoor temp sensor

Table 10-2-3

Operation of diagnostic function

Judgement and action

Check code

Symptom

Unit status

Condition

All stop

All stop

All stop

All stop

All stop

All stop

All stop

All stop

All stop

All stop

All stop

Operation
continues.

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

1. Inverter immediately stops even if restarted.

Compressor rare short

2. Check IPDU.

Cabling error

1. Compressor immediately stops even if restarted.

: Check IPDU.

2. Phase-missing operation of power supply

Check power voltage of R, S, T.

1. Check outdoor temp sensor (TE, TS).
2. Check CDB.

1. Check outdoor temp sensor (TD).
2. Check CDB.

1. Abnormal overload operation of refrigerating

cycle

2. Loosening of screws and contact error of IPDU

and heat sink

3. Cooling error of heat sink
4. Check cabling of CDB and IPDU.

1. Compressor error (Compressor lock, etc.)

: Replace compressor.

2. Cabling trouble of compressor (Phase missing)

1. Check refrigerating cycle. (Gas leak)
2. Error of electron control valve
3. Check pipe sensor (TD).

1. Check power voltage. (AC200V±20V)
2. Overload operation of refrigerating cycle
3. Check current detection circuit at AC side.

1. Overload operation of refrigerating cycle
2. Check outdoor temp sensor (TE).

1. Position detection error
2. Over-current protection circuit operation of

outdoor fan drive unit

Check CDB.

Refer to Judgment of outdoor fan.

1. Position detection circuit operates even if driving

by removing 3P connector of compressor.

Replace IPDU.

1. Check outdoor temp sensor (TO).
2. Check P.C. board.