4 compressor does not operate – Toshiba RAV-SM800XT-E User Manual

Page 59

Advertising
background image

– 57 –

10-4 Compressor does not operate.

<Primary check>

(1) Is the preset temperature higher than the room temperature in cooling operation?
(2) Is the crossover cable connected properly?

<Inspection procedure>

-Cooling only model-

Does miniature relay RY04

switch on and off due to

temperature changes?

Turn on power supply.

Does OPERATION lamp blink?

Are all of compressor

cords normal?

Is compressor motor

winding normal?

(Check winding resistor.)

Is capacitor for

compressor normal?

Is overload relay normal?

Does compressor start?

Does compressor stop

after a while?

Is gas quantity normal?

(Check gas pressure.)

Compressor is defective.

Replace P.C. board.

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

Is resistance value of thermo

sensor (TA) and heat exchanger

sensor (TC) normal?

Microcontroller is defective.

Miniature relay RY04 is defective.

Compressor is defective.

Capacitor is defective.

Overload relay is defective.

Compressor is defective.

Gas shortage (Gas leak)

Refer to 9-6-1 Power

can not be turned on .

Thermo sensor or heat

exchanger sensor

is defective.

Replace thermo

sensor or heat

exchanger sensor.

Replace P.C. board.

Rewire or replace

defective cords.

Replace compressor.

Replace capacitor.

Replace overload relay.

Replace compressor.

Supply gas.

Is it possible to detect

AC 220

240 V between

2

and

3

on the terminal block?