Toshiba RAV-SM800XT-E User Manual

Page 40

Advertising
background image

– 38 –

CAUTION

Do not apply excess torque. Otherwise, the nut
may crack depending on the conditions.

<Tightening connection>

Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.

(Unit : N•m)

Outer diam. of copper pipe

Tightening torque

6.35 mm (diam.)

14 to 18 (1.4 to 1.8 kgf•m)

9.52 mm (diam.)

33 to 42 (3.3 to 4.2 kgf•m)

12.7 mm (diam.)

50 to 62 (5.0 to 6.2 kgf•m)

15.9 mm (diam.)

63 to 77 (6.3 to 7.7 kgf•m)

Flare at
indoor unit side

Flare at
outdoor unit side

Flare nut

Half union

Use a wrench to secure.

Use a torque wrench to tighten.

Externally
threaded side

9-7-3. Pipe Shield for Flare Nut Connection

Joints in liquid and gas pipes of the indoor unit should
be insulated with an attached Pipe shield

$

.

<How to install the pipe shield>

1. Cut the Pipe shield

$

to appropriate length.

2. Set the Pipe shield

$

.

3. In case of a ceiling installation, orient the slit at the

top of the pipe.

4. Fix the Pipe shield

$

with vinyl tape.

Fig. 9-7-5

$

$

$

$

$

Pipe shield

Vinyl tape

Slit

Internally
threaded side

Tightening torque of flare pipe connections

Pressure of R410A becomes higher than that of
R22. (Approx. 1.6 times) Therefore, using a torque
wrench, tighten firmly the flare pipe connecting
sections which connect the indoor and outdoor units
up to the specified tightening torque.

Incorrect connections may cause not only a gas
leakage, but also a trouble of the refrigeration cycle
or compressor damage.

Fig. 9-7-3

Fig. 9-7-4

Advertising
This manual is related to the following products: