UNIREX Pump User Manual

Page 38

Advertising
background image

MARK 3 USER INSTRUCTIONS ENGLISH 71569102 08-06

Page 38 of 68

flowserve.com

The Mark 3 Unitized self-priming centrifugal pumps

have a slightly different requirement regarding

priming. The initial priming liquid must be added to

the pump casing until the liquid has reached the

bottom of the suction nozzle. Once the initial prime is

in place, the pump will automatically replenish itself

and additional priming liquids are not normally

needed. If liquid is lost, additional priming liquid may

be needed.

5.7 Starting the pump

a) Open the suction valve to full open position. It is

very important to leave the suction valve open while

the pump is operating. Any throttling or adjusting of

flow must be done through the discharge valve.

Partially closing the suction valve can create

serious NPSH and pump performance problems.

b)

Never operate pump with both the

suction and discharge valves closed. This could

cause an explosion.

c) Ensure the pump is primed. (See section 5.6.)

d) All cooling, heating, and flush lines must be

started and regulated.

e) Start the driver (typically, the electric motor).

f) Slowly open the discharge valve until the desired

flow is reached, keeping in mind the minimum

continuous flow listed in section 3.4.

g)

It is important that the discharge

valve be opened within a short interval after

starting the driver. Failure to do this could cause

a dangerous build up of heat, and possibly an

explosion.

5.8 Running or operation

5.8.1 Minimum continuous flow

Minimum continuous stable flow is the lowest flow at

which the pump can operate and still meet the bearing

life, shaft deflection and bearing housing vibration limits

documented in the latest version of ASME B73.1M.

Pumps may be operated at lower flows, but it must be

recognized that the pump may exceed one or more of

these limits. For example, vibration may exceed the

limit set by the ASME standard. The size of the pump,

the energy absorbed, and the liquid pumped are some

of the considerations in determining the minimum

continuous flow (MCF).

The minimum continuous flow (capacity) is established

as a percentage of the

best efficiency point

(BEP). (See

section 3.4.4.)

5.8.2 Minimum thermal flow

All Mark 3 pumps also have a

minimum thermal flow

.

This is defined as the minimum flow that will not

cause an excessive temperature rise. Minimum

thermal flow is application dependent.

Do not operate the pump below

minimum thermal flow, as this could cause an excessive

temperature rise. Contact a Flowserve sales engineer

for determination of minimum thermal flow.

Avoid running a centrifugal pump at drastically reduced

capacities or with discharge valve closed for extended

periods of time. This can cause severe temperature

rise and the liquid in the pump may reach its boiling

point. If this occurs, the mechanical seal will be

exposed to vapor, with no lubrication, and may score or

seize to the stationary parts. Continued running under

these conditions when the suction valve is also closed

can create an explosive condition due to the confined

vapor at high pressure and temperature.

Thermostats may be used to safeguard against over

heating by shutting down the pump at a predetermined

temperature.

Safeguards should also be taken against possible

operation with a closed discharge valve, such as

installing a bypass back to the suction source. The size

of the bypass line and the required bypass flow rate is a

function of the input horsepower and the allowable

temperature rise.

5.8.3 Reduced head

Note that when discharge head drops, the pump’s

flow rate usually increases rapidly. Check motor for

temperature rise as this may cause overload. If

overloading occurs, throttle the discharge.

5.8.4 Surging condition

A rapidly closing discharge valve can cause a

damaging pressure surge. A dampening

arrangement should be provided in the piping.

5.8.5 Operation in sub-freezing conditions

When using the pump in sub-freezing conditions

where the pump is periodically idle, the pump should

be properly drained or protected with thermal devices

which will keep the liquid in the pump from freezing.

High chrome iron pumps are not recommended for

applications below -18 °C (0 °F).

Advertising