UNIREX Pump User Manual

Page 23

Advertising
background image

MARK 3 USER INSTRUCTIONS ENGLISH 71569102 08-06

Page 23 of 68

flowserve.com

Figure 4-9 illustrates the ideal piping configuration with a

minimum of 10 pipe diameters between the source and

the pump suction. In most cases, horizontal reducers

should be eccentric and mounted with the flat side up as

shown in figure 4-10 with a maximum of one pipe size

reduction. Never mount eccentric reducers with the flat

side down. Horizontally mounted concentric reducers

should not be used if there is any possibility of entrained

air in the process fluid. Vertically mounted concentric

reducers are acceptable. In applications where the fluid

is completely de-aerated and free of any vapor or

suspended solids, concentric reducers are preferable to

eccentric reducers.

Figure 4-9 Figure 4-10

Avoid the use of throttling valves and strainers in the

suction line. Start up strainers must be removed shortly

before start up. When the pump is installed below the

source of supply, a valve should be installed in the

suction line to isolate the pump and permit pump

inspection and maintenance. However, never place a

valve directly on the suction nozzle of the pump.

Refer to the Durco Pump Engineering Manual and

the Centrifugal Pump IOM Section of the Hydraulic

Institute Standards for additional recommendations

on suction piping. (See section 10.)

Refer to section 3.4 for performance and operating

limits.

4.6.2.1 Mark 3 Self-Priming Pumps

The suction piping must be as short as possible and

be as close to the diameter of the suction nozzle as is

practical. The pump works by removing the air

contained in the suction piping. Once removed, it

operates exactly the same as a flooded suction

standard pump. Longer and larger the suction pipe

have a greater volume of air that has to be removed,

resulting in longer priming time. The suction piping

and seal chamber must be airtight to allow priming to

occur. When possible, it is recommended that

suction piping be sloped slightly towards the casing to

limit priming fluid loss down the suction line during

priming and shutdown.

4.6.3 Discharge piping

Install a valve in the discharge line. This valve is

required for regulating flow and/or to isolate the pump

for inspection and maintenance.

When fluid velocity in the pipe is high,

for example, 3 m/s (10 ft/sec) or higher, a rapidly

closing discharge valve can cause a damaging

pressure surge. A dampening arrangement should

be provided in the piping.

4.6.3.1 Mark 3 Self-Priming Pumps

During the priming cycle, air from the suction piping is

evacuated into the discharge piping. There must be

a way for this air to vent. If air is not able to freely

vent out the discharge pipe, it is typically

recommended to install an air bleed line. The air

bleed line is typically connected from the discharge

pipe to the sump. Car must be taken to prevent air

from re-entering suction pipe.

4.6.4 Allowable nozzle loads

Flowserve chemical process pumps meet or exceed

the allowable nozzle loads given by ANSI/HI 9.6.2.

The following paragraphs describe how to calculate

the allowable loads for each pump type and how to

determine if the applied loads are acceptable. The

first configuration covered is ASME B73.1M pumps,

including the Mark 3 Standard, Sealmatic, Lo-Flo,

Recessed Impeller, and Unitized Self-Priming pumps.

The second configuration covered is the ASME

B73.2M vertical, Mark 3 In-Line pump.

4.6.4.1 Mark 3 horizontal pumps (ASME B73.1M)

The following steps are based upon ANSI/HI 9.6.2.

All information necessary to complete the evaluation

is given below. For complete details please review

the standard.

a) Determine the appropriate casing “Material

Group No.” from figure 3-2.

b) Find the “Casing material correction factor” in

Figure 4-11 based upon the “Material Group No.”

and operating temperature. Interpolation may be

used to determine the correction factor for a

specific temperature.

c) Find the “Baseplate correction factor” in Figure

4-12. The correction factor depends upon how

the baseplate is to be installed.

d) Locate the pump model being evaluated in Figure

4-16 and multiply each load rating by the casing

correction factor. Record the ”adjusted Figure

4-16 loads”.

e) Locate the pump model being evaluated in

Figures 4-17 and 4-18 and multiply each load

rating by the baseplate correction factor. Record

the adjusted Figure 4-17 and 4-18 loads.

Advertising