Creating and Running Algorithms 203

Chapter 6

To set up the algorithms for this example:

1. Define the global variable <cold_setpoint>.

ALG:DEF 'GLOBALS','static float cold_setpoint;'

2. Define the following algorithm language code as ALG1, the ratio

station algorithm.

static float hot_flow, cold_hot_ratio;
static float cold_temp = 55, hot_temp = 180, product_temp = 120;
hot_flow = I108;

/* get flow rate of cold supply */

/* following line calculates cold to hot ratio from supply and product temps */
cold_hot_ratio = (hot_temp - product_temp) / (cold_temp - product_temp);
cold_setpoint = hot_flow * cold_hot_ratio; /* output flow setpoint for ALG2 */

3. Modify a PIDA algorithm so its setpoint variable is the global

variable cold_setpoint, its input channel is I109 and its output channel
is O116 and Define as ALG2, the cold supply flow controller.

/* Modified PIDA Algorithm; comments stripped out, setpoint from global,
inchan = I109, outchan = O116
*/
/* the setpoint is not declared so it will be global */

static float P_factor = 1;

static float I_factor = 0;
static float D_factor = 0;
static float I_out;
static float Error;
static float Error_old;

FT

flow transmitter

ALG2
Flow Controller

ALG1
Ratio Station

flow transmitter

FC

55

°

Cold Supply

GLOBAL

cold_setpoint

I108

O116

I109

180

°

Hot Supply

120

°

Product

Figure 6-4. Inter-algorithm Communication with Globals

FT

RS