Installing remote keypads, Installing, Remote – VistaQuest N7227V5 User Manual

Page 15: Keypads

Advertising
background image

– 15 –

Section 3.

INSTALLING

REMOTE

KEYPADS

This section lists the wired keypads that may be used and provides
instructions for wiring and mounting the keypads.
A preliminary check-out procedure is also provided to ensure that the
connected keypads are functioning properly in the system.

Keypads That May Be Used

Fixed-Word Display: 4127, 4137AD, 6127, 6128, 6137

Alpha Display: 5137AD , 6138, 6139

Up to 4 keypads, independent of auxiliary power considerations (you may
need to use an auxiliary power supply if the 500mA aux. output is
exceeded)

If you are going to use a 4285 Phone module, you MUST use addressable
keypads (4137AD, 5137AD, 6128, 6137, 6138, 6139) in the system, but set to
the non-addressable mode (address 31).

Wiring To The Keypads

1.

Determine wire gauge by referring to the wiring length/gauge chart below.

For devices (Keypads, RF Receivers, etc.) connected to a single 4-wire
run, determine the current drawn by all units connected to the single wire
run, then refer to the Wiring Run chart to determine the maximum wire
length that can be safely used for each wire size. Current draw for all
devices can be found in the

SPECIFICATIONS AND ACCESSORIES

section.

Note:

Refer to “Auxiliary Device Current Draw Worksheet” in the

FINAL

POWER UP section for current draw for all keypads.

Maximum wire lengths for any device that is homerun to the control can also
be determined from the chart, based on the current draw of that device alone.

Wiring Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)

TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN

Wire Size

50mA or less

100mA

300mA

500mA

#22

500 ft (152m)

250 ft (76m)

80 ft (24m)

50 ft (15m)

#20

750 ft (228.6m)

380 ft (116m)

130 ft (39.6m)

80 ft (24m)

#18

1300 ft (396m)

650 ft (198m)

220 ft (67m)

130 ft (39.6m)

#16

1500 ft (457m)

1000 ft (305m)

330 ft (100.5m)

200 ft (70m)

*

Includes Keypads, RF Receivers, Relay Units, or 4285 Phone module.

The length of all wire runs must not exceed 1500 feet (457m) when
unshielded quad conductor cable is used (750 feet if shielded cable is used).
This restriction is due to the capacitive effect

on the data lines when quad

cable is used.

2.

Run field wiring from the control to the keypads (using standard 4 -
conductor twisted wire cable using the wire gauge determined in step 1).

3.

Connect remote Keypads to terminals 4, 5, 6, and 7 on the control board,
as shown in Figure 5.