Acroprint HandPunch 4000 User Manual

Page 18

Advertising
background image

Planning An Installation

16

Figure 2-3: Communication Shielding with All Units Earth Grounded

All units are connected to the same earth ground. Each shield ground is
connected to only one unit, then interrupted to prevent the formation of ground
loops. Two sets of lines are wired as shown in Figure 2-3. It does not matter
significantly which unit’s GND is used for a particular shield, as long as the
path is broken from unit to unit.

The second method of establishing a ground reference in a system with
floating power supplies is to use the ground line in the RS-422 cable to
establish a common reference voltage for the communication signals. This line
should be connected to the negative power terminal on the data converter or
the ground line in the RS-232 port from the host PC system. It should then be
carried to one of the ground terminals on the back of each unit in the network.
An example of this method of grounding is shown in Figure 2-4.

Carry a
Ground Line
to Each Unit

Master

GND T+ T-

Remote 1

GND R+ R-

Remote 2

GND R+ R-

Connect the Cable

Shield to the

Master's Ground

Do Not Connect

the Cable Shield

at this End

Connect the

Cable Shield to

Remote 1's

Ground

Do Not Connect

the Cable Shield

at this End

Connect the

Cable Shield to

Remote 2's

Ground

Do Not Connect

the Cable Shield

at this End

To Next

Remote

Master

GND T+ T-

Remote 1

GND R+ R-

Remote 2

GND R+ R-

Connect the Cable

Shield to the

Master's Ground

Connect Both Shields

to Remote 1 Ground

To Next

Remote

Connect Both Shields

to Remote 2 Ground

Connect Shield

to Next Remote

: Communication Shielding Carrying a Single Ground to Each Unit

If no earth ground is available at the units, this is the only possible method of
connecting the grounds. Even if an earth ground is available, depending on
the building’s power wiring and other environmental issues, this method may
be superior to the previous one, since it establishes the ground of each unit
independently of the building power lines. Local variations in grounds between
buildings, or from one point to another in a very large building, (perhaps due to

Advertising