CABLE SIZING/ RATINGS

208…240 Volt Drives

GWT AQUAVAR CPC

Voltage Phase

NEMA 1

Base

Model

Cont.

Output

Amps

Normal Duty

Horsepower

Frame

Size²

Output

Cable

Min. AWG¹

Input

Cable

Min. AWG¹

Vendor

Part Number

230

1

CPC20171

8.5

2

R1

14

14

ACS550-U1-017A-

2+N2000+P918+X1555

CPC20241

12

3

R2

14

10

ACS550-U1-024A-

2+N2000+X1555

CPC20311

15.5

5

R2

14

8

ACS550-U1-031A-

2+N2000+X1555

CPC20461

23

7.5

R3

12

6

ACS550-U1-046A-

2+N2000+X1555

CPC20591

29.5

10

R3

10

4

ACS550-U1-059A-

2+N2000+X1555

CPC20881

44.0

15

R4

8

2

ACS550-U1-088A-

2+N2000+X1555

CPC21141

57.0

20

R4

6

1/0

ACS550-U1-114A-

2+N2000+X1555

CPC21431

71.5

25

R6

4

3/0

ACS550-U1-143A-

2+N2000+X1555

CPC21781

89.0

30

R6

3

4/0

ACS550-U1-178A-

2+N2000+X1555

CPC22211

110.5

40

R6

2

300 MCM

or 2 x 1/0

ACS550-U1-221A-

2+N2000+X1555

CPC22481

124.0

50

R6

1

350MCM

or 2 x 2/0

ACS550-U1-248A-

2+N2000+X1555

3

CPC20121

11.8

3

R1

14

14

ACS550-U1-012A-

2+N2000+P918+X1555

CPC20171

16.7

5

R1

14

14

ACS550-U1-017A-

2+N2000+P918+X1555

CPC20241

24.2

7.5

R2

12

10

ACS550-U1-024A-

2+N2000+X1555

CPC20311

30.8

10

R2

10

8

ACS550-U1-031A-

2+N2000+X1555

CPC20461

46.2

15

R3

8

6

ACS550-U1-046A-

2+N2000+X1555

CPC20591

59.4

20

R3

6

4

ACS550-U1-059A-

2+N2000+X1555

CPC20751

74.8

25

R4

4

3

ACS550-U1-075A-

2+N2000+X1555

CPC20881

88.0

30

R4

3

2

ACS550-U1-088A-

2+N2000+X1555

CPC21141

114.0

40

R4

2

1/0

ACS550-U1-114A-

2+N2000+X1555

CPC21431

143.0

50

R6

1/0

3/0

ACS550-U1-143A-

2+N2000+X1555

CPC21781

178.0

60

R6

2/0

4/0

ACS550-U1-178A-

2+N2000+X1555

CPC22211

221.0

75

R6

4/0

300 MCM

or 2 x 1/0

ACS550-U1-221A-

2+N2000+X1555

CPC22481

248.0

100

R6

250MCM

or 2 X 1

350MCM

or 2 x 2/0

ACS550-U1-248A-

2+N2000+X1555

NOTE 1: Recommended AWG Size based on NEC table 310.16 , 40º C ambient, 90º C, UL type copper wire. For other wire
sizes or types, consult local, state or NEC codes.
NOTE 2: Frame sizes R7 and R8, the Aquavar CPC will have multiple conductor terminals for each phase. Consult technical
section ( CABLE TERMINALS)

TECHNICAL DATA

The following tables provide current, horsepower, frame size and recommended cable sizes for the Aquavar CPC.

NOTE:

THIS MANUAL SUPERCEDES PAGES 131-135 OF IM167R08.