Technical data, Motor connections, Cooling – r7/r8 – Xylem IM250R03 Aquavar CPC-FD User Manual

Page 32: Cable terminals

Advertising
background image

32

Motor Connections

Motor Connection Specifications – R7/R8

Motor Connection Specifications

Maximum Motor

Frame

Maximum Motor Cable Length*

Cable Length

Size f

sw

= 1 or 4 kHz

f

sw

= 8 kHz or 12 kHz

R7…R8

300 m

980 ft

Does not apply

WARNING! Using a motor cable longer than specified in the chart above may cause permanent
damage to the drive.

Cooling – R7/R8

Cooling Specifications

Method

Internal fan, flow direction from bottom to top.

• R7/R8: Free space in front of enclosure: 152 mm (6 in).

Requirement

• R7/R8: Free space above enclosure: None required for cooling.

• R7/R8: Free space at sides of enclosure: None required for cooling.

• R7/R8: Also see “Additional Free Space Recommendations” on page 33.

Air Flow, 380…480 Volt Drives – R7/R8

The following table lists heat loss and air flow data for 380…480 Volt drives.

Drive

Heat Loss

Air Flow

CPC-xx-

Frame Size

W

BTU/Hr

m

3

/h ft

3

/min

-245A-4

R7

3850

13000

300

540

-316A-4

R8

5300

18000

700

1220

-368A-4

R8

6850

23000

700

1220

-414A-4

R8

7000

24000

700

1220

-486A-4

R8

7600

26000

700

1220

-526A-4

R8

7800

27000

700

1220

-602A-4

R8

8100

28000

700

1220

-645A-4

R8

9100

31000

700

1220

TECHNICAL DATA

Frame

Size

U1, V1, W1
U2, V2, W2

BRK±, UDC± Terminals

Earthing PE Terminal

Minimum

Wire Size

Maximum

Wire Size

Tightening

Torque

Maximum

Wire Size

Tightening

Torque

mm

2

AWG

mm

2

AWG

N

m

lb

ft

mm

2

AWG

N

m

lb

ft

R1

1

0.75

18

10

8

1.4

1

10

8

1.4

1

R2

1

0.75

18

10

8

1.4

1

10

8

1.4

1

R3

1

2.5

14

25

3

2.5

1.8

16

6

1.8

1.3

R4

1

6

10

50

1/0

5.6

4

25

3

2

1.5

R5

1

6

10

70

2/0

15

11

70

2/0

15

11

R6

95

3/0

240

350 MCM

40

30

95

3/0

8

6

1 Aluminum cable cannot be used with frame sizes R1…R6 because of its lower capacity.
Note: See the recommended cable sizes for different load currents in section Cable Sizing/Ratings.

Cable Terminals

(Frames R1-R6)