Technical data – Xylem IM250R03 Aquavar CPC-FD User Manual

Page 28

Advertising
background image

28

500…600 Volt Fuses

500 … 600 Volt

Base

Drive

Frame

Size

Drive Input Fuse Ratings

Vendor

Part Number

HP

Identification

Amps

(600V)

Bussmann

Type

2

CPC5002xFD

R2

15

KTK-R-15

ACS550-PD-02A1-

6+N2000+X1555

3

CPC5004xFD

R2

15

KTK-R-15

ACS550-PD-04A1-

6+N2000+X1555

5

CPC5006xFD

R2

15

KTK-R-15

ACS550-PD-06A1-

6+N2000+X1555

7.5

CPC5009xFD

R2

15

KTK-R-15

ACS550-PD-09A1-

6+N2000+X1555

10

CPC5011xFD

R2

30

KTK-R-30

ACS550-PD-11A1-

6+N2000+X1555

15

CPC5017xFD

R2

30

KTK-R-30

ACS550-PD-17A1-

6+N2000+X1555

20

CPC5022xFD

R3

50

JJS-50

ACS550-PD-22A1-

6+N2000+X1555

25

CPC5027xFD

R3

50

JJS-50

ACS550-PD-27A1-

6+N2000+X1555

30

CPC5032xFD

R4

100

JJS-100

ACS550-PD-32A1-

6+N2000+X1555

40

CPC5041xFD

R4

100

JJS-100

ACS550-PD-41A1-

6+N2000+X1555

50

CPC5052xFD

R4

100

JJS-100

ACS550-PD-52A1-

6+N2000+X1555

60

CPC5062xFD

R4

100

JJS-100

ACS550-PD-62A1-

6+N2000+X1555

75

CPC5077xFD

R6

125

170M1368

ACS550-PD-77A1-

6+N2000+X1555

100

CPC5099xFD

R6

125

170M1368

ACS550-PD-99A1-

6+N2000+X1555

125

CPC5125xFD

R6

160

170M1369

ACS550-PD-125A1-

6+N2000+X1555

150

CPC5144xFD

R6

200

170M1370

ACS550-PD-144A1-

6+N2000+X1555

NOTE: “x” represents both NEMA 1 and NEMA 12 enclosures.

Input Power Cables / Wiring – R7/R8

NEC

Based on:

• NEC Table 310-16 for copper wires

• 40 °C (104 °F) ambient temperature

• 90 °C (194 °F) wire insulation

• Copper cables with concentric copper shield

• Not more than three current-carrying conductors in raceway or cable, or earth (directly buried).

Max Load Current (A) Cu Wire Size (AWG/kcmil)

Max Load Current (A) Cu Wire Size (AWG/kcmil)

345

400 MCM or 2 x 2/0

474

2 x 250

391

500 MCM or 2 x 3/0

534

2 x 300

410

2 x 3/0

615

2 x 350

465

2 x 4/0

711

2 x 500

TECHNICAL DATA