FUSE SIZING/ RATINGS

380…480 Volt Drives

GWT AQUAVAR CPC

Voltage Phase

NEMA 1

Base

Model

Cont.

Output

Amps

Normal Duty

Horsepower

Frame

Size

Input

Current

Amps

Fuse Type³

JJS

Vendor

Part Number

460

3

CPC40061

6.9

3

R1

7.9

10

ACS550-U1-06A9-

4+N2000+P918+X1555

CPC40081

8.8

5

R1

10.1

15

ACS550-U1-08A8-

4+N2000+X1555

CPC40121

11.9

7.5

R1

13.7

15

ACS550-U1-012A-

4+N2000+P918+X1555

CPC40151

15.4

10

R2

17.7

20

ACS550-U1-015A-

4+N2000+X1555

CPC40231

23

15

R2

26.5

30

ACS550-U1-023A-

4+N2000+X1555

CPC40311

31

20

R3

35.7

40

ACS550-U1-031A-

4+N2000+X1555

CPC40381

38

25

R3

43.7

50

ACS550-U1-038A-

4+N2000+X1555

CPC40441

44

30

R4

50.6

60

ACS550-U1-045A-

4+N2000+X1555

CPC40591

59

40

R4

67.9

80

ACS550-U1-059A-

4+N2000+X1555

CPC40721

72

50

R4

82.8

90

ACS550-U1-072A-

4+N2000+X1555

CPC40771

77

60

R5

88.6

100

ACS550-U1-078A-

4+N2000+X1555

CPC40961

96

75

R5

110.4

125

ACS550-U1-097A-

4+N2000+X1555

CPC41241

124

100

R6

142.6

175

ACS550-U1-125A-

4+N2000+X1555

CPC41571

157

125

R6

180.6

200

ACS550-U1-157A-

4+N2000+X1555

CPC41801

180

150

R6

207.0

250

ACS550-U1-180A-

4+N2000+X1555

CPC42451

245

200

R7

281.8

300

ACS550-U1-246A-

4+N2000+X1555

CPC43161

316

250

R7

363.4

400

ACS550-PC-316A-

4+N2000+X1555

CPC43681

368

300

R8

423.2

450

ACS550-PC-368A-

4+N2000+X1555

CPC44141

414

350

R8

476.1

500

ACS550-PC-414A-

4+N2000+X1555

CPC44861

486

400

R8

558.9

600

ACS550-PC-486A-

4+N2000+X1555

CPC45261

526

450

R8

604.9

600

ACS550-U2-526A-

4+N2000+X1555

CPC46021

602

500

R8

692.3

800

ACS550-U2-602A-

4+N2000+X1555

CPC46451

645

550

R8

741.8

800

ACS550-U2-645A-

4+N2000+X1555

NOTE 3: UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type and JJS are
shown in the Aquavar CPC tables. Other manufacturers are acceptable if they meet fuse requirements.

TECHNICAL DATA

The following table provides Aquavar CPC rating information, and recommended fuse sizing for the input short
circuit protection. Branch circuit protection must be provided by the end user, contractor or distributor. Sized
according to local or applicable NEC codes.

NOTE:

THIS MANUAL SUPERCEDES PAGES 131-135 OF IM167R08.