Suitable Mounting Location
For selecting a suitable mounting location for FD configurations, refer to:

• Preparing for installation in the Aquavar CPC User’s Manual, and
• The Technical Data section of this manual for information on dimensions and weights.

Installing the Drive (Supplement to Aquavar CPC User’s Manual - IM167)

WARNING! Metal shavings or debris in the enclosure can damage electrical
equipment and create a hazardous condition. Where parts, such as conduit plates

require cutting or drilling, first remove the part. If that is not practical, cover nearby
electrical components to protect them from all shavings or debris.

Prepare the Mounting Location – R7 and R8

The Aquavar CPC should only be mounted where all of
the requirements defined in “Preparing for Installation”
are met.

Frame sizes R7 and R8 have mounting holes inside
the enclosure base. See “NEMA 1 and 12, R7…R8
Mounting Dimensions” on page 28.

Where it is not possible to use either mounting hole
at the back of the base, use an L-bracket at the top of
the enclosure to secure the cabinet to a wall or to the
back of another enclosure. Bolt the L-bracket to the
enclosure using the lifting lug bolt hole on the top of
the enclosure.

Remove Side Panels – R7 and R8 NEMA 1 and 12 Enclosures

Cabinet Door

1. To open the cabinet door, loosen the quarter-turn screws

that hold the cabinet door closed.

2. Installation access is easier if these panels are kept off

throughout the installation.

PC00023

Fastening points when installed

back against a wall (top view)

Fastening points when installed

back against back

Fastening the cabinet at the top

using L-brackets (side view)

L-bracket

M12 bolt (1/2 to 9/16 in)

Cabinet top

INSTALLATION

R70020

2