Input Power Connections (Supplement to Aquavar CPC User’s Manual)

Fuses

NOTE! Although fuses listed are similar in functional characteristics to fuses listed in
the Aquavar CPC User’s Manual, physical characteristics may differ. Fuses from other
manufacturers can be used if they meet the functional characteristics of those in these
tables.

Drive input fuses are provided to disconnect the drive from power in the event that a
component fails in the drive’s power circuitry.

208…240 Volt Fuses

208 … 240 Volt

Base

Drive

Frame

Size

Drive Input Fuse Ratings

Vendor

Part Number

HP

Identification

Amps

(600V)

Bussmann

Type

1

CPC2004xFD

R1

15

KTK-R-15

ACS550-PD-04A6-

2+N2000+P918+X1555

2

CPC2007xFD

R1

15

KTK-R-15

ACS550-PD-07A5-2

+N2000+X1555

3

CPC2012xFD

R1

15

KTK-R-15

ACS550-PD-012A-2

+N2000+X1555

5

CPC2017xFD

R1

30

KTK-R-30

ACS550-PD-017A-2

+N2000+X1555

7.5

CPC2024xFD

R2

30

KTK-R-30

ACS550-PD-024A-2

+N2000+X1555

10

CPC2031xFD

R2

50

JJS-50

ACS550-PD-031A-2

+N2000+X1555

15

CPC2046xFD

R3

80

JJS-80

ACS550-PD-046A-2

+N2000+X1555

20

CPC2059xFD

R3

80

JJS-80

ACS550-PD-059A-2

+N2000+X1555

25

CPC2075xFD

R4

100

JJS-100

ACS550-PD-075A-2

+N2000+X1555

30

CPC2088xFD

R4

125

170M1368

ACS550-PD-088A-

2+N2000+X1555

40

CPC2114xFD

R4

160

170M1369

ACS550-PD-114A-

2+N2000+X1555

50

CPC2143xFD

R6

200

170M1370

ACS550-PD-143A-

2+N2000+X1555

60

CPC2178xFD

R6

250

170M1371

ACS550-PD-178A-

2+N2000+X1555

75

CPC2221xFD

R6

315

170M1372

ACS550-PD-222A-

2+N2000+X1555

100

CPC2248xFD

R6

315

170M1372

ACS550-PD-248A-

2+N2000+X1555

NOTE: “x” represents both NEMA 1 and NEMA 12 enclosures.