Technical data – Xylem IM250R03 Aquavar CPC-FD User Manual

Page 29

Advertising
background image

29

Drive’s Power Connection Terminals (Supplement to Aquavar CPC User’s Manual)

The following tables show maximum wire size and required tightening torque for incomming
power and motor terminals, and grounding terminal lug information.

208…240 Volt, Terminals

208 … 240 Volt

Frame

Size

Power Wiring Data

Vendor

Part Number

HP Type Code

Circuit

Breaker

Disconnect

Switch

Motor

Terminals

Ground

Lugs

NEMA

1 & 12

1

CPC2004xFD

R1

#10

35 in-lbs

#10

7 in-lbs

#10

12 in-lbs

#10

35 in-lbs

ACS550-PD-04A6-

2+N2000+P918+X1555

2

CPC2007xFD

R1

ACS550-PD-07A5-2

+N2000+X1555

3

CPC2012xFD

R1

ACS550-PD-012A-2

+N2000+X1555

5

CPC2017xFD

R1

ACS550-PD-017A-2

+N2000+X1555

7.5

CPC2024xFD

R2

#6

45 in-lbs

#8

7 in-lbs

#6

12 in-lbs

ACS550-PD-024A-2

+N2000+X1555

10

CPC2031xFD

R2

ACS550-PD-031A-2

+N2000+X1555

15

CPC2046xFD

R3

#3

50 in-lbs

#4

18 in-lbs

#3

24 in-lbs

#3

50 in-lbs

ACS550-PD-046A-2

+N2000+X1555

20

CPC2059xFD

R3

ACS550-PD-059A-2

+N2000+X1555

25

CPC2075xFD

R4

#1

50 in-lbs

#1

55 in-lbs

#1

48 in-lbs

#2

50 in-lbs

ACS550-PD-075A-2

+N2000+X1555

30

CPC2088xFD

R4

350 MCM
274 in-lbs

#1/0 70 in-lbs

#1/0

48 in-lbs

ACS550-PD-088A-

2+N2000+X1555

40

CPC2114xFD

R4

300 MCM
275 in-lbs

ACS550-PD-114A-

2+N2000+X1555

50

CPC2143xFD

R6

350 MCM
360 in-lbs

3 x #3/0

250 in-lbs

ACS550-PD-143A-

2+N2000+X1555

60

CPC2178xFD

R6

ACS550-PD-178A-

2+N2000+X1555

75

CPC2221xFD

R6

2 x 250

MCM

274 in-lbs

2 x 250 MCM

275 in-lbs

ACS550-PD-222A-

2+N2000+X1555

100 CPC2248xFD

R6

ACS550-PD-248A-

2+N2000+X1555

NOTE: “x” represents both NEMA 1 and NEMA 12.