Technical data – Xylem IM250R03 Aquavar CPC-FD User Manual
Page 25
![background image](/manuals/310456/25/background.png)
25
Ratings (Supplement to Aquavar CPC User’s Manual - IM167)
NOTE! The ratings listed below are exceptions to the ratings listed in the Aquavar CPC
User’s Manual.
Ratings, 380…480 Volt Drives
Type Code
Valid up to 40°C (104 °F)
Frame
Size
Vendor
Part Number
Normal Use
Heavy-Duty Use
AQUAVAR CPC-FD -
see below
I
2N
A
P
N
HP
I
2hd
A
P
hd
HP
CPC4245xFD
245
200
192
150
R7
ACS550-PD-246A-
4+N2000+X1555
CPC4316xFD
316
250
240
200
R8
ACS550-PD-316A-
4+N2000+X1555
CPC4368xFD
368
300
302
250
R8
ACS550-PD-368A-
4+N2000+X1555
CPC4414xFD
414
350
368
300
R8
ACS550-PD-414A-
4+N2000+X1555
CPC4486xFD
486
400
414
350
R8
ACS550-PD-486A-
4+N2000+X1555
CPC45261FD
526
450
477
400
R8
ACS550-PD-526A-
4+N2000+X1555
CPC46021FD
602
500
515
450
R8
ACS550-PD-602A-
4+N2000+X1555
CPC46451FD
645
550
590
500
R8
ACS550-U2-645A-
4+N2000+X1555
NOTE:
I
2N
= Motor current draw normal
P
N
= Normal rated power
I
2hd
= Heavy-duty current rating
P
hd
= Heavy-duty NEMA power rating
TECHNICAL DATA