Technical data – Xylem IM250R03 Aquavar CPC-FD User Manual

Page 24

Advertising
background image

24

FUSE SIZING/ RATINGS

600 Volt Drives

GWT AQUAVAR CPC

Voltage Phase

NEMA 1

Base

Model

Cont.

Output

Amps

Normal Duty

Horsepower

Frame

Size

Input

Current

Amps

Fuse Type³

JJS

Vendor

Part Number

575

3

CPC50031

2.7

2

R2

2.7

10

ACS550-U1-02A7-

6+N2000+X1555

CPC50041

3.9

3

R2

3.9

10

ACS550-U1-03A9-

6+N2000+X1555

CPC50061

6.1

5

R2

6.1

10

ACS550-U1-06A1-

6+N2000+X1555

CPC50091

9

7.5

R2

9

15

ACS550-U1-09A0-6

+N2000+X1555

CPC50111

11

10

R2

11

15

ACS550-U1-011A-

6+N2000+X1555

CPC50171

17

15

R2

17

25

ACS550-U1-017A-

6+N2000+X1555

CPC50221

22

20

R3

22

25

ACS550-U1-022A-

6+N2000+X1555

CPC50271

27

25

R3

27

40

ACS550-U1-027A-

6+N2000+X1555

CPC50321

32

30

R4

32

40

ACS550-U1-032A-

6+N2000+X1555

CPC50411

41

40

R4

41

50

ACS550-U1-041A-

6+N2000+X1555

CPC50521

52

50

R4

52

60

ACS550-U1-052A-

6+N2000+X1555

CPC50621

62

60

R4

62

80

ACS550-U1-062A-

6+N2000+X1555

CPC50771

77

75

R6

77

100

ACS550-U1-077A-

6+N2000+X1555

CPC50991

99

100

R6

99

150

ACS550-U1-099A-

6+N2000+X1555

CPC51251

125

125

R6

125

175

ACS550-U1-125A-

6+N2000+X1555

CPC51441

144

150

R6

144

200

ACS550-U1-144A-

6+N2000+X1555

NOTE 3: UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type JJS are
shown in the Aquavar CPC tables. Other manufacturers are acceptable if they meet fuse requirements.

TECHNICAL DATA

The following table provides Aquavar CPC rating information, and recommended fuse sizing for the input short
circuit protection. Branch circuit protection must be provided by the end user, contractor or distributor. Sized
according to local or applicable NEC codes.

NOTE:

THIS MANUAL SUPERCEDES PAGES 131-135 OF IM167R08.

Advertising