FUSE SIZING/ RATINGS

208…240 Volt Drives

GWT AQUAVAR CPC

Voltage Phase

NEMA 1

Base

Model

Cont.

Output

Amps

Normal Duty

Horsepower

Frame

Size

Input

Current

Amps

Fuse Type³

JJN

Vendor

Part Number

230

1

CPC20171

8.5

2

R1

21.3

25

ACS550-U1-017A-

2+N2000+P918+X1555

CPC20241

12

3

R2

30.0

30

ACS550-U1-024A-

2+N2000+X1555

CPC20311

15.5

5

R2

38.8

40

ACS550-U1-031A-

2+N2000+X1555

CPC20461

23

7.5

R3

57.5

60

ACS550-U1-046A-

2+N2000+X1555

CPC20591

29.5

10

R3

73.8

80

ACS550-U1-059A-

2+N2000+X1555

CPC20881

44.0

15

R4

110.0

110

ACS550-U1-088A-

2+N2000+X1555

CPC21141

57.0

20

R4

142.5

150

ACS550-U1-114A-

2+N2000+X1555

CPC21431

71.5

25

R6

178.8

200

ACS550-U1-143A-

2+N2000+X1555

CPC21781

89.0

30

R6

222.5

225

ACS550-U1-178A-

2+N2000+X1555

CPC22211

110.5

40

R6

276.3

300

ACS550-U1-221A-

2+N2000+X1555

CPC22481

124.0

50

R6

310.0

350

ACS550-U1-248A-

2+N2000+X1555

3

CPC20121

11.8

3

R1

13.6

15

ACS550-U1-012A-

2+N2000+P918+X1555

CPC20171

16.7

5

R1

19.2

25

ACS550-U1-017A-

2+N2000+P918+X1555

CPC20241

24.2

7.5

R2

27.8

30

ACS550-U1-024A-

2+N2000+X1555

CPC20311

30.8

10

R2

35.4

40

ACS550-U1-031A-

2+N2000+X1555

CPC20461

46.2

15

R3

53.1

60

ACS550-U1-046A-

2+N2000+X1555

CPC20591

59.4

20

R3

68.3

80

ACS550-U1-059A-

2+N2000+X1555

CPC20751

74.8

25

R4

86.0

100

ACS550-U1-075A-

2+N2000+X1555

CPC20881

88.0

30

R4

101.2

110

ACS550-U1-088A-

2+N2000+X1555

CPC21141

114.0

40

R4

131.1

150

ACS550-U1-114A-

2+N2000+X1555

CPC21431

143.0

50

R6

164.5

200

ACS550-U1-143A-

2+N2000+X1555

CPC21781

178.0

60

R6

204.7

250

ACS550-U1-178A-

2+N2000+X1555

CPC22211

221.0

75

R6

254.2

300

ACS550-U1-221A-

2+N2000+X1555

CPC22481

248.0

100

R6

285.2

350

ACS550-U1-248A-

2+N2000+X1555

NOTE 3: UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type JJN and JJS
are shown in the Aquavar CPC tables. Other manufacturers are acceptable if they meet fuse requirements.

TECHNICAL DATA

The following table provides Aquavar CPC rating information, and recommended fuse sizing for the input short
circuit protection. Branch circuit protection must be provided by the end user, contractor or distributor. Sized
according to local or applicable NEC codes.

Advertising