Single inverter shelf system, 4 single inverter shelf system – Alpha Technologies INEX Inverter System User Manual

Page 19

Advertising
background image

Argus Technologies Ltd.

014-114-C0 Rev D WC

Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS and INEX are registered trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 9 of 43

NOTE:

Use the following table as a guide only. Ensure that the installation complies with the specific wiring rules

applicable to your country or area of jurisdiction.

Shelf number of
2 x 1000VA
inverter
cascaded

Input Current
Maximum
@ 40Vdc

110Vac Output
Current Max.

230Vac Output
Current Max.

Minimum Size
of DC Input
Wire Max.

Min. Size of
110Vac Output
Wire Max.

Min. Size of
230Vac Output
Wire Max.

#1

45.5A

18.2A

8.7A

#8 AWG

#14 AWG

#16 AWG

#2

91.0A

36.4A

17.4A

#4 AWG

#10 AWG

#14 AWG

#3

54.5A

26.1A

#8

AWG

#10

AWG

#4

72.7A

34.8A

#6

AWG

#10

AWG

#5

90.9A

43.5A

#4

AWG

#8

AWG

#6

109.1A

52.2A

#3

AWG

#8

AWG

Shelf number of
2 x 1500VA
inverter
cascaded

Input Current
Maximum
@ 40Vdc

110Vac Output
Current Max.

230Vac Output
Current Max.

Minimum Size
of DC Input
Wire Max.

Min. Size of
110Vac Output
Wire Max.

Min. Size of
230Vac Output
Wire Max.

#1

68.2A

27.3A

13.0A

#6 AWG

#12 AWG

#16 AWG

#2

136.4A

54.5A

26.1A

#2 AWG

#8 AWG

#12 AWG

#3

81.8A

39.1A

#6

AWG

#10

AWG

#4

109.1A

52.2A

#3

AWG

#8

AWG

#5

136.4A

65.2A

#2

AWG

#6

AWG

#6

163.6A

78.3A

#2

AWG

#6

AWG

Table A–Recommended wire size versus current

Remarks: 1. Total Power Rating (VA, W) = No. of shelf × Inverter module power rating (VA, W) * 2

2. I/P current = Total power rating (W) ч 0.88 ч 40

3. O/P current = Total power rating (VA) ÷ AC voltage

4.4

Single Inverter Shelf System

1. In the inverter shelf package, you will find a jumper.

When only ONE inverter shelf is applied in the system, insert
the jumper to pins 1 and 2 of connector JP2:

2. Negative (BAT-) and positive (BAT+) DC input terminal studs are located in the left side of backplane. In

consideration of the power rating and distance from the battery, choose appropriate gauge wire using Table A
as well as local wiring rules.

NOTE:

For inverter systems without a controller, open collector terminals are available on the inverter shelf backplane for

the inverter fail alarm. See details under point 9 of Section 4.5.