Page 26 of 43

6.3.2

Inverter System Parameter Settings

Parameter

Specification

BaudRate: Baud rate of COM port

Selectable at 1) 2400bps, 2) 4800bps and 3) 9600bps

RS422 Addr: RS422 address

RS422 communication protocol

Keypad tones: activation or de-activation
of audio alarm

Selectable at 1) Enable and 2) Disable

Time&Date: Time and Date displayed on
LCD

Time: hh:mm:ss
Date: yyyy-mm-dd

Language English
Brightness: LCD brightness

From 00~63 for adjusting LCD display contrast

Default: Reset Default value

Press “Enter” for resetting the default value and “ESC” cancel the setting
Reset to Default Value (refer to Appendix A)

Dry Connect: Dry contact setting

Refer to Module Parameter Settings section: Dry Contact Setting

Bat Calib: battery voltage calibration

xx.xxV
For regulating the battery voltage value of LCD display of controller after
operating for long period of time.
The adjustable range is from 20.01V to 69.99V

Table F–System parameter settings

6.4

Module Parameter Settings

Parameter

Setting Option

Output volt:
Inverter output voltage

For INV-4810EA/INV-4815EA, selectable at:
1) 208Vac 2) 220Vac 3) 230Vac 4) 240Vac
For INV-4810A/INV-4815A, selectable at:
1) 110Vac 2) 115Vac 3) 120Vac

Output Freq:
Inverter output frequency

Selectable at 1) 50Hz and 2) 60Hz

OPV HL:
High loss of inverter output voltage

For Output volt = 208V, adjustable between 220V and 240V
For Output volt = 220V, adjustable between 233V and 252V
For Output volt = 230V, adjustable between 244V and 264V
For Output volt = 240V, adjustable between 254V and 276V
For Output volt = 110V, adjustable between 117V and 127V
For Output volt = 115V, adjustable between 122V and 132V
For Output volt = 120V, adjustable between 127V and 138V

OPV LL:
Low loss of inverter output voltage

For Output volt = 208V, adjustable between 1760V and 198V
For Output volt = 220V, adjustable between 176V and 209V
For Output volt = 230V, adjustable between 185V and 218V
For Output volt = 240V, adjustable between 193V and 228V
For Output volt = 110V, adjustable between 89V and 105V
For Output volt = 115V, adjustable between 93V and 110V
For Output volt = 120V, adjustable between 100V and 114V

IPV LVSD:
Cut-off voltage of inverter input

Adjustable between 36V and 46V

Power Limited:
Inverter output power capacity

Adjustable between 50% and 100%

Fan Speed:
Fan speed level of inverter module

Selectable at 1) Normal and 2) Full

Inverter On/off:
Setting all/single inverter turn on or off

ON

OFF

I nv: X

Serial No:
xxxxxxxxx

ON

OFF

Single

Enter

Table G–Inverter parameter settings

1. All ->On/Off
2. Single
Serial No:
xxxxxxxxxx
On

Off

Advertising