Specifications for INEX Inverter System

Argus Technologies Ltd.

014-114-B1 Rev D WC

Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS and INEX are registered trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 1 of 4

Inverter Module Input

Nominal Voltage:

48Vdc


Operating Range:

40.5 to 58Vdc within rated limits


Under Voltage Warning Threshold:

45Vdc


Under Voltage Threshold:

40Vdc


Over Voltage Warning Threshold:

58Vdc


Over Voltage Threshold:

60Vdc


Isolation AC-DC:

Reinforced isolation (Pri-Sec) 4242Vdc/1min


Inrush current:

<2*Irated


Isolation DC-enclosure:

707Vdc (varistors and filter capacitor removed)/1min


Input Protection:

Reverse polarity protection


Psophometric Noise Voltage:

≤1.0mV ITU-T O.41 (16.66 to 6000Hz)


Reflected Psophometric Noise Current: <1% according to YD/T 777-2006

Reflected Relative Band Width Current Noise: <10% (0-2MHz) according to YD/T 777-2006

Wide Band Noise:

<1.0mV (psophometric, 25Hz to 5kHz)
<20mVrms (25Hz to 20kHz)


Peak to Peak Noise:

<150mV up to 100MHz


Inverter Module Output

Power Capacity:

1000VA/800W,
1500VA/1200W


Waveform:

Pure sine wave


Power Factor:

0.8


Nominal Output Voltage:

110/115/120Vac or 208/220/230/240Vac


Voltage Regulation:

Max ±2%


Output Frequency:

50/60Hz


Frequency Variation:

Max ±0.5%


Frequency Setting:

Manually, field-selectable


Crest Factor:

3:1


T.H.D. (Current):

<3% for linear load, <5% for non-linear load


Capacitive/Inductive Load:

-0.8 to +0.8 without exceeding permissible distortion for resistive load


Efficiency:

Min 88% at rated load for 48Vdc system