Alarm Type

Alarm Name

Level

Remark

Inverter fault

Major

Inverter fault

Inv over load

Observe

Inverter Over-loading

Inv fan fault

Major

Inverter Fan fault

Inv low volt off

Major

Inverter shut down due to low input voltage

Inv Bus High

Critical

Bus voltage over the maximal level

Inv Bus Low

Critical

Bus voltage under the minimal level

Inv BusSoft fail

Critical

Bus Soft Start Fail

Inv Output short

Critical

Inverter Output Short

Inv OPV Low

Critical

Inverter output voltage low

Inv OPV High

Critical

Inverter output voltage high

Inv Temp High

Critical

Inverter Temperature High

NegPow Protect

Critical

Inverter negative power protection

SynPulse fault

Critical

Sync Pulse Fault

Inv EPO

Critical

EPO

SoftStart fail

Critical

Inverter soft start fail

Eeprom fail

Major

Inverter EEPROM fault

Inverter

Inv Temp High

Critical

Inverter temperature high

Inv unavailable

Major

Inverter unavailable

Main unavailable

Major

Mains unavailable

Output overload

Major

Output over load

OP Short circuit

Critical

Output short circuit

K1 Relay open

Major

Back-feed relay open

STS SCR1 short

Critical

SCR1 short circuit

STS SCR2 short

Critical

SCR2 short circuit

INV Bypass Mode

Critical

Inverter bypass mode

Over temperature

Major

STS temperature high

MBS Abnormal

Critical

MBS in abnormal position

STS Fan Lock

Major

STS fan fault

STS fault mode

Critical

STS running in fault mode

STS Eeprom Fault

Major

EEPROM fault

SPS Power Fail

Critical

Control power fail

STS

OutPut Abnormal

Critical

STS output normal

Inv lost

Critical

Inverter lost

STS lost

Critical

STS lost

DC input low

Critical

Bat Volt Low

Cont temp high

Critical

Controller temperature High

Cont eeprom fail

Major

Controller EEPROM fault

DC input Over

Critical

Bat voltage high

Controller

CAN Bus Off

Critical

Controller CAN bus off

Table O–Alarm code factory defaults