Specifications for INEX Inverter System Continued

Argus Technologies Ltd.

014-114-B1 Rev D WC

Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS and INEX are registered trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 2 of 4

Current Limitation:

Electronic current limitation at overloads and short circuits


Isolation AC-enclosure:

Basic isolation (Pri-Gnd) 2121Vdc/1min


Surge Protection:

EN61000-4-5, Telcordia GR-1089 CORE, ANSI/IEEE C62.41, STD 587-
1980


Dynamic Response:

Better than ±10% according to IEC 62040-3 Class 1


Over Load Protection:

1.5*Inom >20s
1.25*Inom temperature controlled
Inom = 1000VA/output voltage
Short circuit current = 16A for INV-4810EA and 30A for INV-4810A


Load Sharing:

<5%


Inverter Protection

Over Load:

When load exceeds 150% of power capacity, inverter will shut down after
20 seconds, and diagnose as overload fault with red LED lit.
When load is 105~150%, inverter continuously delivers output power
with a yellow LED lit for warning.


Output Voltage Fault Detection:

When the output RMS (root mean square) voltage is out of operating
voltage range, the inverter unit will diagnose as output voltage high or
low fault.


Inverter Output Short Circuit:

When output RMS voltage is below 40VAC and output RMS current is
over 2A, the system will diagnose as inverter output short circuit fault
with red LED on.


Input Voltage Detection:

When the DC input voltage is out of operating voltage range, the inverter
system will shut down and release visual and audio alarms.


Over Temperature:

When inverter internal temperature rises over 100°C (212°F), the system
will diagnose as over temperature fault with red LED flicker.


Maximum Number of INEX Inverter Modules for Parallel Connection

Model

With STS-050A

Without STS-050A

INV-4810A (1000VA/120Vac)

6

12

INV-4810EA (1000VA/240Vac)

12

12

INV-4815A (1500VA/120Vac)

4

8

INV-4815EA (1500VA/240Vac)

8

12

Note: Static transfer switch (STS)

INEX Controller Module

DC Nominal Voltage:

48Vdc


DC Voltage Range:

30 to 70Vdc


Over Current Protection:

2A fuse


LCD Display:

3” backlit LCD screen with 4 lines by 16 characters


LED Indicators:

Green/normal, yellow/warning, and red/fault