Inverter Module LED Display Status

Priority

Green LED

LED Signal

Status

Solid

STS work Normally

Blink (slow)

Running mode not accord with setting
priority, for example, STS work in off-line
mode, but the priority is on-line

Blink (fast)

STS work in Inverter bypass mode (the
internal mode of STS, not mean IBP of MBS)

Priority

Yellow LED

LED Signal

Status

Solid

Mains or Inverter abnormal

Blink (fast)

If the status of green LED is the same as
yellow LED, then it stands for Inverter bypass
mode, otherwise it means Back-feed relay
open

Blink (fastest)

STS Output abnormal

Priority

Red LED

LED Signal

Status

Blink (slow)

Fan lock or CAN communication fail or
EEPROM fault

Blink (fast)

SCR short or auxiliary power supply fault

Blink (fastest)

MBS position abnormal

Solid

STS Fault mode, maybe overload or over
temperature or output short

NOTE:

If more than one warning exists at the same time, then the LED will display the highest priority.

Table T–STS LED indicator display


Alarm Priority

LED Indicator Status

Observe

Green: On

Yellow: On

Red: off.

Major

Green: On

Yellow: off

Red: On

Critical

Green: On

Yellow: off

Red: On

Buzzer chirp

Table U–Operating sequence troubleshooting table