Parameter

Setting Option

AC HL: High loss of alternative AC input

xxxV

AC LL: Low loss of alternative AC input

xxxV

Inv HL: High loss of inverter AC input

xxxV

Inv LL: Low loss of inverter AC input

xxxV

Priority

Selectable at 1) On line and 2) Off line

Table H–STS parameter settings

6.4.1 Fan

Speed

Control

Output current and NTC temperature decide the fan speed. The NTC temperature has the influential priority.
When the temperature is above 70ºC, the fan will work in full speed. However, when the temperature is less than
60ºC, the fan works according to the different load current. The fan has four levels of speed, the following tables
show the relation between fan speed and load current:

Load

Detect Back

Speed

Duty

Load > 75%

Speed1

100%

75% ≥ Load > 50%

<=70%

Speed2

2/3

50% ≥ Load > 25%

<=45%

Speed3

1/3

25% ≥ Load

<=20%

Speed4

0

Table I–One fan, rotate speed1

Load

Detect Back

Speed

Duty

Load > 75%

Speed1

2/3

75% ≥ Load > 50%

<=70%

Speed2

1/3

50% ≥ Load > 25%

<=45%

Speed3

1/4

25% ≥ Load

<=20%

Speed4

0

Table J–Two fans, rotate speed2

Relation between fan speed and load current: