7 Default

Values

Setting

Default Value

STS priority

On-line

Mains high loss volt

138V

Mains low loss volt

100V

Inverter input high loss volt for STS

138V

Inverter input low loss volt for STS

100V

Inverter output high loss volt

138V

Inverter output low loss volt

100V

Inverter shutdown due to low input volt

40V

Inverter shutdown due to high input volt

60V

Inverter output volt

120V

Inverter output volt frequency

60Hz

Inverter output power limit

100%

Table L–120Vac system factory defaults


Setting

Default Value

STS priority

On-line

Mains high loss volt

264V

Mains low loss volt

185V

Inverter input high loss volt for STS

264V

Inverter input low loss volt for STS

185V

Inverter output high loss volt

264V

Inverter output low loss volt

185V

Inverter shutdown due to low input volt

40V

Inverter shutdown due to high input volt

60V

Inverter output volt

230V

Inverter output volt frequency

50Hz

Table M–230Vac system factory defaults


Setting

Default Value

RS-232, RS-422, RS-485 communication baud rate

2400bps

RS-422 address

9999

Button tone

On

LCD brightness value

45

Language English
Password 1234
Dry contact 1

Inverter overload

Dry contact 2

Inverter unavailable

Dry contact 3

Inverter fan fault

Dry contact 4

STS fan fault

Dry contact 5

Inverter power limit

Table N–System parameter factory defaults