Positioner 1067, 3 installation – Burkert Type 1067 User Manual
Page 66

E-14-
POSITIONER 1067
g) Place the cursor of the path-measuring system into the groove "
9" of the spindle "8" of the feed-
back/positional transducer and set this spindle onto the spindel of the actuator. Fasten screw "
10".
h) Insert electronic board "
2" into the slot of the positioner housing.
i) Inside the housing, connect plug "
1" of the path-measuring system to the connector of the electro-
nic board, with respect to the wire colours (blue mark)
j) Cut cable "
12" at the desired length and pull it through the cable gland "7" of the external feedback/
positional transducer.
k) Connect cable "
12" to the connector of the electronic board:
-
:
brown
A
:
white
+
:
green
l) Tighten the cable gland "
7".
m) Screw the housing "
11" of the external feedback/positional transducer.
+
-
A
1
2
4
5
6
7
8
12
3
9
10
11
Fig. 17 Diagram for the assembly of positioner variant 3 and external feedback/positional
transducer