Positioner 1067, 4 operation – Burkert Type 1067 User Manual

Page 83

Advertising
background image

POSITIONER 1067

E-31-

4 OPERATION

DEADBND

(factory setting : DBD = 0.5%): Deadband around the system deviation

The DEADBND additional function enables the response of the actuator to occur only after a specific
system deviation [DBD] (Fig. 32). This „protects“ the servo valve.

Fig. 32 Deadband DBD

Control
difference

Set position

Actual position

To the controller

Rangeability:

Maximum 5% relative to the stroke range.

The bottom limit is determined by AUTOTUNE.

CLTIGHT

(factory setting: CLT = 0.5%): Closed tight function.

The closed tight function ensures that the valve is tightly closed outside the control range.

Fig. 33 Closed tight function

programmable from 0,0 to 10,0%

programmable from 90,0 to 100%

Plug travel (%)

Set position (%)

CLT

: Closed tight threshold

Specification of a value (%) from which the actuator air is completely exhausted (at 0%) or supplied
with air (at 100%). The opening or resumption of the control operation takes place with a hysteresis of
1% (refer to Fig. 33).
Setting range:
0.0 ... 10.0% (applies both for complete exhausting as well as for complete air supply, see Fig. 33).