POSITIONER 1067

5.1 Fault

messages

Faults during switch on

Message Possible

cause

Remedy

INT.ERROR

Internal fault

Not possible, unit defective

Fault messages during AUTOTUNE function

Message Possible

cause

Remedy

TURN POT

Range of the position transducer exceeded

Remove the positioner from

(only with internal feedback transducer option)

the actuator,and turn

the transducer from 180°. cf fig 2.

ERR 2

Actuator not adjustable

Fit the positioner with

Opening time < 0.5 s

bigger air chambers.

Reduce the air pressure

ERR 3

Actuator volume is too big

use a positioner with valves

(opening time > 30 sec.)

connected in parallel

ERR 4

Miscellaneous failure causes:

- manual operation of valve not

- Check manual actuation

in basic setting

parameters

- no air pressure connected

- Check compressed air supply

- position transducer not connected

- Check the electrical connection

of the transducer;If internal position

control system only.(cf fig. 2)

Check the mechanical coupling

of the position controler;if external

position control system (cf fig. 3)

5 MAINTENANCE

5.2

Spare parts ordering codes

Designation Order

code

Electronic board

553183

Power supply board, if connected to single-acting valve type 27xx

553184

Power supply board, if connected to single-acting valve type Namur

553185

Power supply board, if connected to double-acting valve type Namur

553186

Set of 2 rocker valves, DN0,6

553423

Set of 2 rocker valves, DN0,9

553424

Set of 2 rocker valves, DN1,2