Installation – Fulton Vertical Coil (FT-C_S) Thermal Fluid (hot oil) Heater User Manual

Page 11

Advertising
background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

SECTION 2

FTCS-IOM-2013-1114

INSTALLATION

2-5

TABLE 1 - SPECIFICATIONS - COIL DESIGN THERMAL FLUID HEATER

Model FT-C

0080

0120

0160

0240

0320

0400

0600

0800

1000

1200

1400

Heat Output

1000 BTU/HR

1000 KCAL/HR

800
200

1,200

300

1,600

400

2,400

600

3,200

800

4,000
1,000

6,000
1,500

8,000
2,000

10,000

2,500

12,000

3,000

14,000

3,500

Thermal Fluid Content

GAL

LITERS

10
38

21
80

19
72

31

116

68

258

76

288

132
498

171
648

290

1,097

383

1,448

460

1,741

Recommended Flow Rate

GPM

M3/HR

50

11.4

75
17

100

22.7

150

34

250

56.8

250

56.8

375

85.2

500

113.6

615
139

730
167

800
182

Typical Circulating Pump Motor

HP

KW

10

7.5

10

7.5

15

11.2

15

11.2

20

14.9

20

14.9

30

22.5

40

29.5

50

37.3

50

37.3

60
45

Typical Burner Motor*

HP

KW

1.5
1.1

3

2.2

3

2.2

3

2.2

5

3.7

5

3.7

7.5
5.6

15

11.2

20
15

20
15

20
15

Fuel Consumption @
Full Output No.2 Oil

GPH

LITER/HR

7.1

27

10.7
40.6

14.3
54.1

21.4

81

28

108.8

35.3

136

53

201

69.3

263.7

87.1

329.6

104.5
395.5

122

461.5

Natural Gas

FT3/HR

M3/HR

998

38.3

1,498

42.4

1,998

56.5

2,999

84.9

4,000
113.2

4,997
141.5

7,498
212.3

9,997

283

12,496

353.8

14,998

424.6

17,500

495.5

* Std burner, single fuel applications.
Notes:
Voltage 3 Phase for Burner and Pump - Each unit has an incorporated stepdown transformer. Fuel up to No. 6 Oil Available for Large Units (FT-0600-C and larger). Effi

ciency up to 80%

Minimum Based on High Heating Value of the Fuel (No. 2 Oil @ 140,000 BTU/GHHV; Natural Gas @ 1000 BTU/ft3HHV. Modulation 3 to 1 Turn Down Ratio (5 to 1 for 320). Optional on FT-0080, 0120,
and 0160-Standard on all others. Circulating pump motor sizes based on standard pressure (55 PSIG) and viscosity 1 cs, specifi c gravity 0.7, with 25-37 PSID available head for installation.

TABLE 2 - DIMENSIONS-COIL DESIGN THERMAL FLUID HEATER (SEE FIGURE 2)

Model FT-C

0080

0120

0160

0240

0320

0400

0600

0800

1000

1200

1400

Heater Inlet/ Outlet Connections

IN

MM

1.25

32

1.5

38

2

51

2.5

64

3

76.3

3

76

4

102

4

102

6

152

6

152

6

152

(A) Overall Height

IN

MM

73.7

1,872

80.7

2,050

80.6

2,046

89.7

2,278

100.6
2,556

112.4
2,856

143.6
3,648

143

3,632

146.5
3,721

146.4
3,718

163.1
4,144

(B) Overall Width

IN

MM

31.6

803

34.4

873

45.9

1,165

50.1

1,273

49.3

1,252

49.3

1,252

63.4

1,611

70.5

1,791

95

2,413

108.4
2,753

108.4
2,753

(C) Overall Depth

IN

MM

46.2

1,173

60.6

1,540

60.6

1,540

66.6

1,691

80.6

2,046

80.6

2,046

88.1

2,237

107.75

2,736

135.1
3,432

152.9
3,882

152.9
3,882

(D) Flue Outlet Diameter

IN

MM

10

254

10

254

10

254

12

305

14

356

14

356

18

457

20

508

20

508

22

559

22

559

Recommended Vertical
Stack Diameter

IN

MM

10

254

12

304

12

304

14

356

18

457

18

457

22

558

24

609

24

609

26

661

26

661

Approximate Dry Weight

LBS

KG

1,500

700

2,100

950

2,550
1,150

3,400
1,550

5,300
2,400

5,300
2,400

8,250
3.750

11,450

5,200

19,250

8,750

21,700

9,850

23,000
10,455