Operation, Operating limit controller, On/off controls – Fulton Vertical Coil (FT-C_S) Thermal Fluid (hot oil) Heater User Manual

Page 64: Modulating controls, Pressure gauges

Advertising
background image

© The Fulton Companies 2013

3-24

OPERATION

FTCS-IOM-2013-1114

SECTION 3

!

WARNING

To ensure that your Fulton equipment
is kept operating safely and
effi

ciently, follow the maintenance

procedures set forth in this manual.

The end user of the heater must
maintain all labels on the heater
in clean, legible condition. All
connections and safety devices, both
mechanical and electrical, must be
kept clean, with ease of access for
inspection, use and maintenance.

Operating Limit Controller

The limit controller is mounted in the panel box door. This limit controller senses
temperature in the outlet manifold. The temperature setpoint in the controller
may be adjusted per manufacturer’s instructions.

On/Off Controls

Typically one controller is provided to sense the temperature on the heater
outlet. This controls the operation of the heater by switching it on and off .

1. An adjustable two point diff erential between shut off and start up is

built into the controller. This prevents frequent cycling of the burner. The
controller is set to provide the desired outlet fl uid temperature. Due to the
temperature rise through the unit, this may be considerably higher than
the inlet temperature.

2. If the unit is equipped with an on/off controller, it will be located on the

face of the electrical cabinet. The temperature setpoint in the controller
can be adjusted following the manufacturer’s instructions.

Modulating Controls

All coil models are standardly equipped with modulating controls.

1. The modulating temperature controller continuously regulates the outlet

fl uid temperature between the minimum fi ring rate and high fi re. When
the unit is on low fi re and the temperature continues to climb past the
setpoint, the heater will shut down. It will typically re-start when the
process temperature drops 7°F below setpoint.

2. Minimum load depends on the degree of modulation provided. Typically

3:1 or 5:1 modulation is provided, depending on the fuel selection and
heater size. In this case minimum load is one third of full fi ring rate.

3. The modulating temperature controller is set to maintain the desired fl uid

outlet temperature. Due to the temperature rise across the heater, this may
be considerably higher than the inlet temperature.

4. If the unit is equipped with a modulating controller, it will be located on

the face of the electrical cabinet. The temperature setpoint in the controller
can be adjusted following the instructions in the component data sheet
section of this manual.

Pressure Gauges

All units have two pressure gauges measuring the thermal fl uid pressure at the
inlet of the heater and at the outlet of the heater. A third gauge measures the
pump suction pressure.

1. The

diff erence between the readings of the two gauges indicates the

pressure loss across the heater. The diff erence must not fall below the
recommended value. Recommendations are based on heater size and are
listed in manual and on the product data submittals on www.fulton.com.

Advertising