Installation – Fulton Vertical Coil (FT-C_S) Thermal Fluid (hot oil) Heater User Manual

Page 12

Advertising
background image

© The Fulton Companies 2013

2-6

INSTALLATION

FTCS-IOM-2013-1114

SECTION 2

!

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

A qualifi ed installer, service agency
or the gas supplier must perform
installation and service on the fuel
delivery system.

Do not use matches, candles, fl ame or
other sources of ignition to check for
gas leaks.

WHAT TO DO IF YOU SMELL GAS:
Do not try to light the appliance.
Do not touch any electrical switch.
Do not use any phone in the building.
Leave building and contact gas
supplier from neighbor’s phone. If you
cannot reach gas supplier, phone the
fi re department.

When making gas piping joints,
maintain proper ventilation to reduce
breathing hazards.

An exhaust fan may draw products of
combustion into the work environment
creating a possible hazard to personnel.

4

CAUTION

It is essential that only fresh air be
allowed to enter the combustion air
system. Foreign substances, such
as combustible volatiles and lint in
the combustion system can create
hazardous conditions. If foreign
substances can enter the air stream, the
combustion air inlet must be piped to
an outside location. Failure to do so will
void the warranty.

To avoid failures due to poor
combustion, ensure make-up air system
is properly designed.

3. Ensure the equipment room air supply openings are kept clear at all times.

4. See Table 5 for minimum make-up air required and the recommended area

of each opening for each model.

TABLE 3- APPROXIMATE FLOOR LOADING

Model

Heater Only*

FT-0080C

500

FT-0120C

400

FT-0160C

450

FT-0240C

450

FT-0320C

450

FT-0400C

450

FT-0600C

550

FT-0800C

500

FT-1000C

500

FT-1200C

400

FT-1400C

450

FT-0400S

675

FT-0600S

675

FT-0800S

525

*All weights are lbs/ft

2

TABLE 4 - RECOMMENDED MINIMUM CLEARANCES FOR PERSONNEL ACCESS/BURNER

REMOVAL

Model

Inches (Meters)

FT-0080C

109 (2.8)

FT-0120C

115 (3.0)

FT-0160C

119 (3.1)

FT-0240C

125 (3.2)

FT-0320C

133 (3.4)

FT-0400C

145 (3.7)

FT-0600C

171 (4.4)

FT-0800C

172 (4.4)

FT-1000C

173 (4.4)

FT-1200C

172 (4.4)

FT-1400C

188 (4.8)

FT-0400S

162 (4.2)

FT-0600S

170 (4.4)

FT-0800S

171 (4.4)

5. If positive forced ventilation is adopted, ensure that there will be no

appreciable pressure variation in the equipment room.

6. Avoid ventilation which creates a negative pressure in the building as it

will seriously aff ect combustion and proper operation of the stack. Please
note that exhaust fans or similar equipment can create a down draft in the
chimney or starve the burner’s air supply. Either case may result in poor

Advertising