Installation, Warning – Fulton Vertical Coil (FT-C_S) Thermal Fluid (hot oil) Heater User Manual

Page 26

Advertising
background image

© The Fulton Companies 2013

2-20

INSTALLATION

FTCS-IOM-2013-1114

SECTION 2

!

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.

TABLE 8 - RECOMMENDED LOADS FOR JM CLIPPER ELASTOGRAPH 150# GASKETS SAE

GRADE 5 BOLTS OR EQUAL

Nominal Flange Size

(inches)

Number of Bolts

Diameter of Bolts

(inches)

Preferred Torque Req.

Per Bolt (ft-lb)

1/2

4

1/2

30

3/4

4

1/2

30

1

4

1/2

30

1 1/4

4

1/2

30

1 1/2

4

1/2

30

2 4

5/8

60

2 1/2

4

5/8

60

3 4

5/8

60

4

8

5/8

60

5

8

3/4

100

6

8

3/4

100

8

8

3/4

100

10

12

7/8

160

TABLE 9 - RECOMMENDED LOADS FOR JM CLIPPER ELASTOGRAPH 300# GASKETS SAE

GRADE 5 BOLTS OR EQUAL

Nominal Flange Size

(inches)

Number of Bolts

Diameter of Bolts

(inches)

Preferred Torque Req.

Per Bolt (ft-lb)

1/2

4

1/2

30

3/4

4

5/8

60

1

4

5/8

60

1 1/4

4

5/8

60

1 1/2

4

3/4

100

2 8

5/8

60

2 1/2

8

3/4

100

3 8

3/4

100

4

8

3/4

100

5

8

3/4

100

6

12

3/4

160

8

12

7/8

245

10

16

1

160

Advertising