Installation – Fulton Vertical Coil (FT-C_S) Thermal Fluid (hot oil) Heater User Manual

Page 15

Advertising
background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

SECTION 2

FTCS-IOM-2013-1114

INSTALLATION

2-9

8. During any pressure testing of the system at pressures

in excess of 1/2 psig (14 inch W.C.)., disconnect the
heater at the heater manual shutoff valve (located at
the end of the supplied gas train) from the gas supply
piping system.

9. Ensure the supply pressure is regulated by a non-

stacking, tight, shut-off regulator.

10. Arrange gas piping so that it does not interfere with

any cover or burner, inhibit service or maintenance,
or prevent access between unit and walls or another
unit.The burner assembly and gas controls terminate
at a manual stop valve to which the gas supply should
be connected. Piping must be sized for a gas fl ow
consistent with the required BTU/Hr input. Large
pressure drops must be avoided. Fulton recommends
that the supply piping between the pressure regulator
and the inlet to the heater be kept to a minimum. The
minimum required gas pressure at the stop valve varies

0-400 PSIG

RETURN

TO LOW PRESSURE OIL

SWITCH ON CONTROL PANEL

RETURN

TO TANK

PUMP

INLET

MODULATING

OIL VALVE

(IF APPLICABLE)

CHECK
VALVE

BURNER

BURNER

1/4" NPT

CHECK VALVE

OIL S.S.O.V.

MOUNTED

TO SKID

MOUNTED TO
TOP OF UNIT

PI

PI

0-200 PSIG

1/4" COPPER
TUBING

SUPPLY

NC OIL VALVE

PRESSURE
INDICATOR

FUEL
OIL PUMP

INLET

RETURN

MODULATING
OIL VALVE

MOUNTING
BRACKET

3/8” COPPER TUBING
OR ½” SCHEDULE 40
CARBON STEEL PIPING

3/8” COPPER TUBING
OR ½” SCHEDULE 40
CARBON STEEL PIPING

FIGURE 5 - TYPICAL NO. 2 OIL FIRED FUEL TRAIN

with the model of heater. The requirements for natural
gas-fi red coil design models are as follows:

 Models FT-0080-C to FT-0400-C 14”w.c.

 Models FT-0600-C to FT-0800-C

60”w.c.

 Models FT-1000-C to FT-1400-C

120”w.c.

NOTE:

Note: Low emissions burners for all models

require 5 psi.

NOTE:

Even when the unit is shut down, the gas supply

pressure must never exceed these values.

NOTE:

When operating, the supply pressure must not drop

below these limits: Not less than 11 “ w.c. where 14” w.c is
required. Not less than 50” w.c. where 60” w.c. is required.
Not less than 100” w.c. where 120” w.c. is required.

Advertising