INSTALLATION

FTCS-IOM-2013-1114

SECTION 2

!

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

Combination Deaerator/Thermal Buff er/Expansion Tank

Fulton Thermal’s effi

cient design combines the operation of the expansion,

deaerator, and thermal buff er tanks. Installation is considerably simplifi ed by
virtue of this arrangement.

The expansion section is vital to the thermal fl uid system. From ambient to
operating temperature, the thermal fl uid in the system will typically expand
in the range of 25% to 50%, and a vessel capable of handling this expansion is
mandatory. The customer should confi rm the expansion rate of the chosen fl uid
and system volume.

At start up, the primary purpose of the deaerator section is to remove all volatiles
from the system to avoid pump cavitation. The deaerator section also allows air
to be vented from the system on a continuous basis during operation to avoid
oxidation of the thermal fl uid, and removes other volatile particles generated by
the fl uid itself during system operation. This section of the tank must be insulated.

Vent for Piping

to Safe Catchment

Expansion

Tank

Liquid

Level

Switch

Fluid Out

Fluid In

Deaerator

Section

Thermal
Buffer
Section

Hot Fluid

Medium Fluid

Cool Fluid

Gases (Steam)

Expansion

Volume

Drain

FIGURE 13 - EXPANSION TANK DETAILS

Model

Capacity (gallons)

Initial Fill (gallons)

Available for

Expansion (gallons)

Max System Volume

FT-200-L

52

25

46

184

FT-500-L

132

40

121

525

FT-1000-L

264

80

232

1000

FT-1500-L

397

90

380

1400

FT-2000-L

528

145

444

1700

FT-3000-L

793

215

717

2600

FT-5000-L

1310

300

1168

4600