3-18

OPERATION

FTCS-IOM-2013-1114

SECTION 3

!

WARNING

Do not operate, or allow others
to operate, service or repair this
equipment unless you (they) fully
understand all applicable sections
of this manual and are qualifi ed to
operate/maintain the equipment.

9. Once all the points have been verifi ed, press Escape until you are back to

the main menu.

10. You can observe the status of the burner by going to OperationalStat

>NormalOperation.

11. Turn the main ON/OFF switch to OFF. The control will now postpurge.

Verify ignition using steps from Setting Main Burner Ignition with the new
gas pressures.

12. Turn the main burner switch to OFF. The control will now post purge.

13. Under

Manual Operation > Auto/Manual/Off , change the operation

to Automatic and press Enter and confi rm Automatic is entered in the
current fi eld.

14. Press

Escape twice to get back to the main menu.

15. Under

Updating >ParamBackup, select LMV51 – AZL. This will store all

of the adjustments that have been made in the LMV base module to the
display. If the base module fails in the future, the display can be used to
download all of the parameters into a new base module.

16. The heater is now ready to run. Adjust your setpoint on the temperature

control to the desired temperature and turn the main ON/OFF switch to
ON for the burner to operate.

CHANGING SET POINT ON THE AZL

1. Hit

Escape to Select Operation than hit Enter and scroll to Heater Set

point, hit Enter to Set point W1 hit Enter and enter new set point with
Select buttons.

2. When accomplished hit Enter than Escape 3 times to Operational Stats

hit Enter to Normal Operation, hit Enter to get to the main screen.

FOR MANUAL OPERATION

1. Hit

Escape and scroll to Manual, hit Enter to Auto / Manual / Off , change

to Manual and hit Escape to Set Load, change to 0 or desired load range
with the select buttons.

2. When

in

Manual it will allow you to go to any load range to verify

combustion.

3. When done hit Escape and scroll to Operational Stats, hit Enter to

Normal Operation, hit Enter to main screen.

4. To return back to Auto operation repeat step 1 & 2.

5. Please refer to this manual’s addendum for information on specifi c LMV 51

control parameters.

NOTE:

DO NOT leave unit unattended in Manual Operation, in this mode

the LMV 51 will ignore its internal Set Point.