Operation, High and low fluid pressure switches – Fulton Vertical Coil (FT-C_S) Thermal Fluid (hot oil) Heater User Manual

Page 61

Advertising
background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

3-21

SECTION 3

FTCS-IOM-2013-1114

OPERATION

!

WARNING

Do not operate, or allow others
to operate, service or repair this
equipment unless you (they) fully
understand all applicable sections
of this manual and are qualifi ed to
operate/maintain the equipment.

Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.

of loss of fl ow.

3. The

diff erential pressure switch can be tested while only the pump is

running at operating temperature. Remove the metal cover on top of the
switch and increase the setpoint until the pump shuts down. This value
should be greater than the DP of the gauges. Next, decrease the setpoint
back to its initial value and depress the pump start button to verify the
pump will re-start.

High and Low Fluid Pressure Switches

The heater is equipped with a low inlet, high inlet and high outlet pressure
switch. See Figure 6. The switches are located on the side of heater panel with
tubing connections to the respective heater inlet and outlet manifolds. The
switches are used to ensure proper fl ow through the heater (no restrictions in the
piping system). The switches must be set at startup and the setpoints are based
on the system design/performance.

The only pressure required in the thermal fl uid system is the pressure required
to maintain the proper fl ow. Pressure changes are monitored with these
switches, which will shut the unit down in case of a change in the fl uid fl ow.

TO TEST THE SWITCHES

1. With three position switch set to “Pump”, remove the cover from the

pressure switch and manually trip the switch. Pump should shut down.

2. Repeat for each switch; replace covers. Note, if the burner was on, it would

also stop.

3. To set the inlet low fl uid pressure cutout switch, raise the setpoint with

the fl uid at operating temperature and pump running, until the pump
shuts down. Note the setpoint and lower by 10 PSI, then restart pump. The
setpoint at cutout should correspond to the reading on the inlet pressure
gauge.

FIGURE 24 - HIGH/LOW GAS PRESSURE SWITCH

Advertising