Maintenance, Safety check procedures – Fulton Vertical Coil (FT-C_S) Thermal Fluid (hot oil) Heater User Manual

Page 74

Advertising
background image

© The Fulton Companies 2013

4-6

MAINTENANCE

FTCS-IOM-2013-1114

SECTION 4

!

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

4

CAUTION

All maintenance procedures should
be completed by trained personnel.
Appropriate training and instructions
are available from the Fulton Service
Department at (315) 298-5121 or your
local Fulton Thermal Representative.

Soot Cleaning

If your coil inspection indicates severe sooting, the following procedure should
be followed:

1. Make sure the heater is off and fl uid is ambient temperature.

2. Remove the burner and lower access doors.

3. Wire brush coils and use compressed air where accessible.

4. Vacuum loose soot where accessible.

5. Reinstall the burner and lower access doors.

6. Fire the heater and set combustion.

Safety Check Procedures

Perform the following safety checks as needed:

Liquid Level Switch

Manually turn liquid level switch cam counterclockwise. See Figure 15. Micro-
switch will open contacts and control voltage will be lost. Release cam and
micro-switch will make and control voltage will be restored.

Stack Limit

The limit manufacturer presets the stack limit. Testing can be performed by
removing switch from stack and applying heat over that of the switch set point
for several seconds. The switch can then be reset and re-installed. See Figure 29.

FIGURE 29 - STACK LIMIT SWITCH

Manual Reset

Advertising