Operation, Fill the system, Filling procedure for systems open to atmosphere – Fulton Vertical Coil (FT-C_S) Thermal Fluid (hot oil) Heater User Manual

Page 43

Advertising
background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

3-3

SECTION 3

FTCS-IOM-2013-1114

OPERATION

!

WARNING

Pressurizing a drum to force fl uid into
the system is not recommended. The
drum may explode, creating a hazard
to personnel and equipment.

During operation, any leaks are
usually detected by a small amount
of vapor. Leaks should be attended
to as soon as possible because under
certain circumstances, such as
saturated insulation, thermal fl uid can
ignite when exposed to air and heat.

4

CAUTION

Do not use this equipment if any part
has been under water (or subjected to
heavy rains/water if the equipment does
not have NEMA 4 wiring, controls and
instrumentation). Immediately call a
qualifi ed service technician to inspect
the equipment and to replace any
part of the control system and/or gas
control(s) which have been under water.

Commissioning/Start up by a non-
Fulton authorized person will void the
product warranty.

Please read these instructions and
post in an appropriate place near the
equipment. Maintain in good legible
condition.

The system pump is not to be used to fi ll
the system.

A pump that has been used for water
or a diff erent thermal system should
not be used prior to extensive cleaning.
Thermal fl uid may be damaged by
contact with moisutre of other fl uids.

Fill the System

The viscosity of thermal fl uid is generally very high (500 cS) at ambient
temperature. Below 50°F (10°C) some fl uids become very thick. Fluid should be
in a pumpable liquid form prior to fi lling the system. Refer to the thermal fl uid
manufacturer’s recommendations.

Adhere to the following when fi lling the system:

1. Refer to Figure 17 for the drain and fi ll connection.

1. Filling must be carried out from the lowest point in the system in order to

prevent air pockets from forming.

2. A drain and fi ll point (generally a 3/4” threaded coupling) is provided on

the inlet to the pump suction on skid-mounted units.

3. Typically a portable, high velocity pump, such as the type used for

chemical transfer, is appropriate for fi lling the system. Where only one or
two drums of fl uid are required, a handheld pump may be practical.

Filling Procedure for Systems Open to Atmosphere

Adhere to the following:

1. Follow the instructions in Fill The System section of this manual.

2. Check to see that the liquid level switch operates freely. To confi rm

operation of the liquid level switch, manually trip the liquid level switch.
Unit should shut down; pump will stop.

3. Fill the system slowly, closing all opened bleed and drain valves as fl uid

reaches them.

4. When the fl uid reaches and fl ows from the expansion tank low level

manual test connection, begin slowing down the fi lling process.

5. Close the low level connection and continue to fi ll until the liquid level

switch closes. After fl uid appears in the low level connection, only a small
amount of additional fl uid should be required.

6. If

fl uid is observed coming from the expansion section high level manual

test connection, drain fl uid from the tank until the level is between the
liquid level switch and the high level connection.

7. Filling is complete when the fl uid has reached the lowest level in the

expansion tank required to actuate the liquid level switch.

8. As oil reaches a vent, close it. After all vents have been closed, and you

believe the system to be full, stop fi lling. Start the circulating pump as
described in Initial Start-Up: Cold Circulation section of this manual.
Leave the fi ll equipment connected as cleaning the strainer may create the
need for more oil in the system.

9. Verify to see that the liquid level switch operates freely. To confi rm

operation of the liquid level switch, manually trip the liquid level switch.
Unit should shut down; pump will stop.

Advertising