OPERATION

!

WARNING

Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.

10. Under

Auto/Manual/Off , change the operation to Burner On by using the

arrow keys. Press enter and verify that “Burner On” is acknowledged in the
current fi eld.

11. Press

Escape twice to get back to the main menu.

12. Turn the main burner switch Local or On position.

13. Increase the set point. Under operation-Heater set point go to setpoint

W1 using the arrow key then press Enter. Change the set point under new,
using the arrows and press Enter. The new set point should appear under
actual and displayed in degrees.

14. After several seconds the burner control will start its pre-ignition phase and

the blower will start.

15. You can observe the status of the burner by going to the main menu (by

pressing Escape) then selecting Operational Stat > Normal Operation.

16. The unit will purge then drive to the ignition position and the pilot should

light.

17. The burner control will stay at this pilot hold stage so you can inspect and

adjust the pilot as needed.

18. The pilot gas pressure should match the test fi re sheet.

19. The

fl ame signal should be greater than 90% when viewed from the top

menu of the Siemens AZL display.

20. Once the pilot is adjusted properly and you are ready to light the main

burner, press Escape to the main menu.

SETTING MAIN BURNER IGNITION

1. Under

Params&Display >RatioControl >ProgramStop, change the

Program Stop to 52 Interv2. This is the main burner ignition position. Press
Enter and confi rm that 52 Interv2 is acknowledged in the current fi eld. This
change moves the control to the main burner ignition point in the burner
sequence.

2. This will allow the main burner to ignite. Should the burner not light, the gas

and air servo motors are not synchronized to produce a combustible mix.

3. Turn

the ON/OFF switch on the panel box to OFF.

4. To reset the alarm: Press Escape on the AZL once. Press Enter on the AZL to

reset the control. The red light should go out.

5. To change the setting, return to the front menu by pressing Escape until

you are to the main menu. Then select Params&Display >RatioControl
>GasSettings >SpecialPositions > IgnitionPos
, adjust the gas servo
position by using the arrow key to move down to Gas servo if needed. Press
Enter to select the servo. Move the gas servo to its new position with the
arrow keys. Press Enter to confi rm the new value. Use the down arrow to
move to the air servo setting if needed. Press Enter to select the servo, use the
arrow keys to set the new value. Press Enter to confi rm this.