CALIBRATION

PROCEDURES FOR RIO

Normal Calibration

1. Set the Control Word to either Automatic (0x000)

or Manual (0x0001). Clear all other bits in the

Control Word.

2. Set the New Pulses Per Liter to zero.

3. Execute a BTW to start the calibration.

4. Execute a Null BTW, specifying a Type 07

BTR, followed by a BTR until Calibration

(Population) Completed Bit (0x8000) is set or

the Calibration (Population) Failed Bit (0x4000)

is set.

5. Accept actual quantity flowed from operator

input and calculate the New Pulses Per Liter

value based on the elapsed time.

6. Set either the Update PPL for Current Job

(0x0002) or Update PPL for All Jobs (0x0004)

bit and clear all other bits in the Control Word.

7. Execut a BTW to write the New Pulses Per

Liter to complete the calibration.

8. To abort the calibration procedure, set the Stop

Calibration (Population) (0x8000) bit in the

Control Word and issue a BTW.

Lookup Table Population

1. Set the Control Word to Lookup Table Popu-

lation (0x0008).

2. Execute a BTW to start the population se-

quen- ce.

3. Issue repeated BTR's until the Calibration

(Population) Completed bit (0x8000) is set, or

the Calibration (Population) Failed (0x4000) bit

is set.

4. To abort the Population procedure, set the Stop

Calibration (Population) (0x8000) bit in the

Control Word and issue a BTW.