RIO Starting Quarter

The Starting Quarter within the rack must also be

specified in order for the ASIC to communicate

over the RIO link.

The RIO Starting Quarter is specified in SW1, po-

sitions 7 and 8 as shown below. (Factory default

settings in bold)

SW1-7

SW1-8

OFF

OFF

ON

ON

OFF

ON

OFF

ON

0

1/4

1/2

3/4

Starting

Quarter

RIO Baud Rate

The RIO Baud Rate must also be specified in order

for the ASIC to communicate over the RIO link.

The RIO Baud Rate is specified in SW1, positions

3 and 4 as shown below. (Factory default settings

in bold)

SW2-3

SW2-4

OFF

OFF

ON

ON

OFF

ON

OFF

ON

57.6 Kbaud

115.2 Kbaud

230.4 Kbaud

230.4 Kbaud

Baud Rate

RIO Non-Used Switch Settings

There are several switches that are either not used

presently, or have a function that is not involved

with RIO. They are noted here for clarity. (Factory

default settings in bold)

Switch

ON

SW2-1

SW2-2

SW2-5

SW2-6

Normal Operation

Master Channel

Outputs Gun

Flow Rate

See SIO Baud Rate

See SIO Baud Rate

Reset CMOS RAM

to factory defaults

Master Channel

Outputs Master

Channel Flow Rate

See SIO Baud Rate

See SIO Baud Rate

OFF

RIO Cable Connections

The RIO Connection is made using Allen-Bradely

"Blue Hose." The connections are made at the

rear of the DynaFlow back-plane on connector

J8. If the DynaFlow rack is the last rack on the

"Blue Hose," insert a 120 ohm, 1/8th watt resis-

tor across terminals J8-12 and J8-14 in order to

properly terminate the RIO cable to avoid standing

waves which cause communication noise. This

is extremely important for higher baud rates and

industrial environments.

PLC RIO

Cable

120 Ohm, 1/8th

Watt Terminating

Resistor

Blue

Shield

Clear

J8-12

J8-13

J8-14

Between this termi-

nal....

Shield(s) Only

....and this terminal.

DynaFlow

Back-Plane

47

DynaFlow

Programer's Manual - Installation

Ransburg

LN-9406-00.3