Vector R Series Cascade Applicators - Operation

Ransburg

26

SETPOINT VOLTAGE

The Vector spray applicator system has three volt-

age setpoints 1, 2, and 3. Each of these voltages

can be individually adjusted between 20 and full

kV using the + and - buttons on the front of the

control unit. When the applicator trigger is off,

the present setpoint can be changed either from

the control unit or from the switch on the back of

the applicator.

†

Setpoints cannot be adjusted

below 20 kV.

NOTE

Figure 5: Front View of Control Unit

POWERING UP

CONTROL UNIT

When the AC power is turned on, the unit will

display the PC board applicator type number on

the kV setpoint display and the software revision

level in the µA display for 2-3 seconds.

Figure 4: Control Unit Start-Up Display

Description

Applicator Type

1
5

START-UP DISPLAY

85 kV Cascade
65 kV Cascade

†

DO NOT connect a 65 kV applicator to

a unit setup for 85 kV. Damage to 65 kV

barrel assembly may occur.

C A U T I O N

!

Setting and Changing the Setpoint

at the Control Unit

From the factory, Preset 1 is full minus 20 kV,

Preset 2 is full kV minus 10, and Preset 3 is full

kV. For 79500/79523 full kV is 85 kV. For 79501

full kV is 65 kV.

At the control unit with the applicator not triggered,

press the 1, 2, or 3 button on the front panel of

the control unit. (See Figure 5 for positions of the

kV setpoint and adjust buttons.) The only place to

adjust the kV of each setpoint is at the control unit.

OPERATION

AH-06-01.13