The position complete output will turn ON when the controller becomes ready following the power ON.
To check if the controller is ready, always check if the position complete output is ON.
The actuator will not operate unless the pause input is turned ON.
T1: 6 msec or more; time after selecting/entering a command position until the start input turns ON

(The scan time of the host controller must be considered.)



Note: When the start signal turns ON, the position complete output will turn OFF.

The start signal must be turned OFF with the confirmation that the position complete output
has turned OFF while the start signal remains ON.

If the start input remains ON as shown below, the position complete output will not turn ON
even when the actuator movement is completed.














Command position

Start

Position complete

Home return completion

Speed

Actuator movement

Position 1

Positioning band

Time

Note

Mechanical end Home

T

1

Start

Position complete


Actuator

Movement is complete.