75

If the actuator does not perform home return, confirm that the *pause signal is ON, the motor-drive power
supply is receiving power, and no error messages are displayed, among others.


(10) Set the target position, speed, acceleration/deceleration, positioning band and other data in the position

table. For details on how to set data in the position table, refer to the operation manual for the teaching
pendant or PC software, whichever is applicable.

Now, you can operate the actuator automatically via control from the PLC.

Note: Move the actuator to the target position after confirming that the *ALM output is ON and the

motor drive power is supplied.




Timing chart at start




































Motor-drive power
supply


Input of 24-VDC
power supply




LED lamp



Alarm output (*ALM)


Pause input (*STP)




Home return

Cut off

Supplied

Initial parameter setting

Red

Green

Pause is released.

Move

ment st

arts

Mech

ani

cal e

nd

H

ome

po

si

tion

Create a position table
via teaching pendant or
PC operation.